Project ID: 994671 DEA: 010H8004 EFIS: 0118000110
QA Service Level: 1
DIST-CO-RTE-PM: 01-HUM-254-4.3/4.7
Work Description: Project Name: Myers Flat Permanent Restoration
Location Description: Bridge No. 04E0041
Contractor Name: McCullough Construction Inc.
Contractor Address: 57 Alder Grove Road, Arcata, CA 95521
Resident Engineer: Brian Apple Structure Rep.: Alexander Mattson
DIME Sample ID: 2023-10-14-9
TL Number from the TL Form:
Sample Submitted By Organization: CT D01 - Boyd Road Field Laboratory
Sample Organization Contact: (707) 496-0974
Type of Sample: Department Acceptance
Type of Material: Concrete
Sample Taken Date: 10/14/2023
Date that the sample was received by the laboratory/organization performing the testing: 10/16/2023
The quantity of what the sample constitutes: 50 yards
A brief description of the sample: 6 4x8 Cylinders
From where was the sample collected: Job Site
Laboratory sample identification: C0234
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Eureka Ready Mix Alton
The concrete mix design number: E400F
The truck number from where the sample was collected: 84
The batch plant ticket number from where the sample was collected: 20590
Concrete batch plant: Eureka Ready Mix Alton
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: chute
Where the material sample would have been placed if not sampled: Miranda Soldier Pile Wall Whaler 1
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-10-14-9-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 10/21/2023
Date Tested: 10/21/2023
Submitted By Organization: CT D01 - District 1 Materials Laboratory
Organization Address: 1726 Albee Street,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: leif.ayres@dot.ca.gov
Organization Phone: (707) 496-0974
General Comments for this Test: 7 Day Break 10/21/23
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.6 in^2
|
Cross sectional area of cylinder 2
|
12.6 in^2
|
Cross sectional area of cylinder 3
|
12.6 in^2
|
Compressive strength (to nearest 10 psi)
|
3500 psi
|
Maximum load on cylinder 1
|
43700 lb
|
Maximum load on cylinder 2
|
43820 lb
|
Maximum load on cylinder 3
|
44400 lb
|
Type of fracture pattern of cylinder 1
|
5
|
Type of fracture pattern of cylinder 2
|
5
|
Type of fracture pattern of cylinder 3
|
5
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
7 days
|
Age of specimen in hours
|
0 hours
|
DIME Test ID: 2023-10-14-9-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/11/2023
Date Tested: 11/11/2023
Submitted By Organization: CT D01 - District 1 Materials Laboratory
Organization Address: 1726 Albee Street,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: leif.ayres@dot.ca.gov
Organization Phone: (707) 496-0974
General Comments for this Test: 28 Day Break 11/11/23
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.6 in^2
|
Cross sectional area of cylinder 2
|
12.6 in^2
|
Cross sectional area of cylinder 3
|
12.6 in^2
|
Compressive strength (to nearest 10 psi)
|
5250 psi
|
Maximum load on cylinder 1
|
66040 lb
|
Maximum load on cylinder 2
|
63970 lb
|
Maximum load on cylinder 3
|
67830 lb
|
Type of fracture pattern of cylinder 1
|
5
|
Type of fracture pattern of cylinder 2
|
5
|
Type of fracture pattern of cylinder 3
|
5
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|