Project ID: 993685 DEA: 09382304 EFIS: 0919000038
QA Service Level: 1
DIST-CO-RTE-PM: 09-KER,MNO-395-Var
Work Description: FURNISH AND INSTALL SIGN STRUCTURE (TRUSS); AND PLACE AND MODIFY CMS.
Location Description: KERN AND MONO COUNTIES AT VARIOUS LOCATIONS
Contractor Name: ALFARO COMMUNICATIONS CONSTRUCTION, INC.
Contractor Address: 15614 S Atlantic Ave, Compton, CA 90221
Resident Engineer: Monty Navarro Structure Rep.: Derek Armon
DIME Sample ID: 2023-10-12-25
TL Number from the TL Form:
Sample Submitted By Organization: CT D09 - Bishop Field Laboratory
Sample Organization Contact: (760) 872-5211
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 10/12/2023
Date that the sample was received by the laboratory/organization performing the testing: 10/13/2023
The quantity of what the sample constitutes: 20 cubic yards
A brief description of the sample: 5000 Psi Mix
From where was the sample collected: Job Site
Laboratory sample identification: Conc-01
Structure unique identifier:
Structure name: CMS Foundation
The fabricator/manufacturer/facility name: Mammoth Ready Mix
The concrete mix design number: 1304.18.25.A
The truck number from where the sample was collected: 74
The batch plant ticket number from where the sample was collected: 55958
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: CMS Foundation Upper 10 feet
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-10-12-25-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 10/19/2023
Date Tested: 10/19/2023
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: PCC-01
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
3.5 lb
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
1880 psi
|
Maximum load on cylinder 1
|
23410 lb
|
Maximum load on cylinder 2
|
23800 lb
|
Compressive strength of cylinder 1
|
1860.0 psi
|
Type of fracture pattern of cylinder 1
|
1
|
Compressive strength of cylinder 2
|
1890.0 psi
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Correction factor for cylinder 2
|
1.00
|
Age of specimen
|
7 days
|
Age of specimen in hours
|
0 hours
|
Serial number of delivery ticket, if available
|
no data
|
DIME Test ID: 2023-10-12-25-2
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/13/2023
Date Tested: 11/09/2023
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test:
Test Result Compliance: does not comply
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
3.5 lb
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
3420 psi
|
Maximum load on cylinder 1
|
49960 lb
|
Maximum load on cylinder 2
|
42100 lb
|
Maximum load on cylinder 3
|
37020 lb
|
Compressive strength of cylinder 1
|
3970.0 psi
|
Type of fracture pattern of cylinder 1
|
1
|
Compressive strength of cylinder 2
|
3350.0 psi
|
Compressive strength of cylinder 3
|
2950 psi
|
Type of fracture pattern of cylinder 2
|
1
|
Type of fracture pattern of cylinder 3
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Correction factor for cylinder 2
|
1.00
|
Correction factor for cylinder 3
|
1.00
|
Age of specimen
|
0 days
|
Age of specimen in hours
|
0 hours
|
Serial number of delivery ticket, if available
|
PCC-01
|
DIME Test ID: 2023-10-12-25-3
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/28/2023
Date Tested: 11/27/2023
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: PCC-01
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
3.5 lb
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
4190 psi
|
Maximum load on cylinder 1
|
52650 lb
|
Maximum load on cylinder 2
|
51660 lb
|
Maximum load on cylinder 3
|
53780 lb
|
Compressive strength of cylinder 1
|
4190.0 psi
|
Type of fracture pattern of cylinder 1
|
1
|
Compressive strength of cylinder 2
|
4110.0 psi
|
Compressive strength of cylinder 3
|
4280 psi
|
Type of fracture pattern of cylinder 2
|
1
|
Type of fracture pattern of cylinder 3
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Correction factor for cylinder 2
|
1.00
|
Correction factor for cylinder 3
|
1.00
|
Age of specimen
|
46 days
|
Age of specimen in hours
|
0 hours
|
Serial number of delivery ticket, if available
|
no data
|