Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 994441 DEA: 081A8304 EFIS: 0800000579 COOP: 081746
QA Service Level: 2
DIST-CO-RTE-PM: 08---
Work Description: Widening the existing Cedar Avenue overcrossing (OC) from 6 to 10 lanes, replacing the Union Pacific Railroad overhead (OH), widening Cedar Avenue from 4 to 6 through lanes, and realigning and/or widening the interchange entrance and exit ramps
Location Description: At the Interstate 10 (I-10) Cedar Avenue Interchange from PM 17.8 to 19.3 in the County of San Bernardino (County)
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Kee Ooi Structure Rep.: Matt Bruce
DIME Sample ID: 2023-10-09-27
TL Number from the TL Form:
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Verification
Type of Material: Asphalt Binder
Sample Taken Date: 10/09/2023
Date that the sample was received by the laboratory/organization performing the testing: 10/11/2023
The quantity of what the sample constitutes: 1 Can
A brief description of the sample: JMF Verification
From where was the sample collected: Source
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Vulcan Corona
Performance Grade: PG 64-28 M
Modified: Yes
Lot number:
Sublot number:
Tank number:
Time of sample:
HMA Supplier:
Certified Asphalt Supplier: Seventeen Twenty Oil Company - Corona CA
Multigrade: No
Multigrade Type:
Asphalt Binder Mix Number:
DIME Test ID: 2023-10-09-27-1
Test Method: AASHTO T228-22: Standard Method of Test for Specific Gravity of Semi-Solid Asphalt Materials (Specific Gravity)
Verified Date: 11/04/2023
Date Tested: 10/11/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance: not applicable
Additional Comments When Verified:
DIME Test ID: 2023-10-09-27-2
Test Method: AASHTO T240-17: Standard Method of Test for Effect of Heat and Air on a Moving Film of Asphalt Binder (Rolling Thin-Film Oven Test)
Verified Date: 11/04/2023
Date Tested: 10/11/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test: - 1.013 + 0.006 = - 01.007
Test Result Compliance: complies
Additional Comments When Verified:
Is mass change based on one or two containers?
|
Two
|
Any material loss from containers during heating process/testing?
|
No
|
Mass of empty container #1
|
170.722 grams
|
Mass of empty container #2
|
172.893 grams
|
Mass of container #1 before test (m1i)
|
205.505 grams
|
Mass of container #2 before test (m2i)
|
207.822 grams
|
Mass of container #1 after test (m1f)
|
205.157 grams
|
Mass of container #2 after test (m2f)
|
207.464 grams
|
Average mass change
|
-1.013 percent
|
DIME Test ID: 2023-10-09-27-3
Test Method: AASHTO T315-12: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 11/04/2023
Date Tested: 10/11/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
Original binder
|
Phase Angle (δ) (for the 10 cycles)
|
66.4 degree
|
Dynamic Shear, G*/sin(δ)
|
1.78 kPa
|
(G*) x sin(δ)=
|
no data
|
DIME Test ID: 2023-10-09-27-4
Test Method: AASHTO T315-16: Standard Method of Test for Determining the Rheological Properties of Asphalt Binder Using a Dynamic Shear Rheometer (DSR) (Dynamic Shear)
Verified Date: 11/04/2023
Date Tested: 10/11/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Phase
|
RTFO residue
|
Test Plate Diameter
|
25 mm
|
Phase Angle (δ) (for the 10 cycles)
|
70.7 degree
|
Dynamic Shear, G*/sin(δ)
|
3.34 kPa
|
DIME Test ID: 2023-10-09-27-5
Test Method: AASHTO T316-17: Standard Method of Test for Viscosity Determination of Asphalt Binder Using Rotational Viscometer
Verified Date: 11/04/2023
Date Tested: 10/11/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Is viscosity reading in cP/Pa-s?
|
Pa-s
|
Time of test
|
9:20 HH:MM
|
Test Temperature
|
135 C
|
Speed
|
50 rpm
|
Spindle size
|
21 in
|
Torque
|
71.2 %
|
Viscosity reading #1 (A)
|
0.722 Pa-s
|
Viscosity reading #2 (B)
|
0.704 Pa-s
|
Viscosity reading #3 (C)
|
0.71 Pa-s
|
Average viscosity
|
0.712 Pa-s
|
DIME Test ID: 2023-10-09-27-7
Test Method: AASHTO T44-18: Standard Method of Test for Solubility of Bituminous Materials
Verified Date: 11/04/2023
Date Tested: 10/11/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Was test performed on residue from distillation or evaporation?
|
NA
|
Soluble, percent
|
99.5 %
|
Insoluble, percent
|
0.5 %
|