REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Jason Trinh |
Date Reported: |
05/18/2016 |
|
Address: |
TL Number: |
250002 |
||
City: |
||||
Project Name: CONSTRUCT SOLDIER PILE RETAINING WALL AND RECONSTRUCT SHOULDER.. |
||||
Prime Contractor: GORDON N. BALL, INC. |
||||
Sample Taken Date: |
04/20/2016 |
Mix Design: |
1533941 |
|
Contractor: Unknown |
Location: CONSTRUCT SOLDIER PILE RETAINING WALL AND RECONSTRUCT SHOULDER. |
|||
Structure unique identifier: Unknown |
||||
Structure name: Unknown |
||||
Location of Pour: Unknown |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 6.01 | 28.37 | 131875 | 4648.4 | 2 |
2 | 6.01 | 28.37 | 129855 | 4577.2 | 2 |
DIME Test ID: 2016-04-20-7-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 4610
Age of specimen: 28 days
Certified By: Bang Nguyen
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing