DEPARTMENT OF TRANSPORTATIONDIVISION OF ENGINEERING SERVICES MATERIALS ENGINEERING AND TESTING SERVICES Concrete Materials Testing Branch 5900 Folsom Blvd. Sacramento, CA 95819 916-227-7205 |
Contract # 040A7724 Cty ALA Rte 80 PM 6.4/6.8 Vendor # |
REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Maxime Dabilly |
Date Reported: |
10/18/2023 |
|
Address: |
TL Number: |
|
||
City: |
||||
Project Name: Excavation, HMA, structural concrete, minor concrete and drainage. |
||||
Prime Contractor: OC Jones (Will Dieterich) |
||||
Sample Taken Date: |
09/20/2023 |
Mix Design: |
4E0CG5E1 |
|
Contractor: Unknown |
Location: IN BERKELEY AND ALBANY FROM 0.6 MILE NORTH OF UNIVERSITY AVENUE OVERCROSSING TO 0.3 MILE SOUTH OF EL CERRITO SEPARATION AND OVERHEAD |
|||
Structure unique identifier: |
||||
Structure name: Retaining Wall 175 |
||||
Location of Pour: |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 5.89 | 27.25 | 108379 | 3978.0 | 1 |
2 | 5.90 | 27.34 | 116636 | 4266.0 | 4 |
DIME Test ID: 2023-09-20-2-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 4120
Age of specimen: 28 days
Certified By: Spencer Adams
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing