Gavin Newsom, Governor |
DEPARTMENT OF TRANSPORTATIONDIVISION OF ENGINEERING SERVICES MATERIALS ENGINEERING AND TESTING SERVICES Concrete Materials Testing Branch 5900 Folsom Blvd. Sacramento, CA 95819 916-227-7205 |
Contract # 033E1004 Cty PLA Rte 80 PM 8.1/37.8 Vendor # |
REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Martin Clark |
Date Reported: |
04/07/2016 |
|
Address: |
TL Number: |
131315 |
||
City: |
||||
Project Name: IMPROVING VERTICAL CLEARANCE |
||||
Prime Contractor: RGW Construction Inc |
||||
Sample Taken Date: |
04/05/2016 |
Mix Design: |
J7A8545LL |
|
Contractor: Unknown |
Location: PLACER COUNTY IN AND NEAR LOOMIS, PENRYN, NEWCASTLE, WEIMAR, AND MAGRA FROM 0.1 MILE WEST OF BRACE ROAD OVERCROSSING TO 0.1 MILE EAST OF MAGRA OVERCROSSING |
|||
Structure unique identifier: Unknown |
||||
Structure name: Unknown |
||||
Location of Pour: Pedestals |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 6.02 | 28.46 | 97856 | 3438.4 | 1 |
2 | 6.02 | 28.46 | 96353 | 3385.6 | 1 |
DIME Test ID: 2016-04-05-2-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 3410
Age of specimen: 2 days
Certified By: Mike Mullins
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing