DEPARTMENT OF TRANSPORTATIONDIVISION OF ENGINEERING SERVICES MATERIALS ENGINEERING AND TESTING SERVICES Concrete Materials Testing Branch 5900 Folsom Blvd. Sacramento, CA 95819 916-227-7205 |
Contract # 040J3004 Cty SON Rte 1 PM 26.7/27.1 Vendor # |
REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Fabio La Serna |
Date Reported: |
10/06/2023 |
|
Address: |
TL Number: |
|
||
City: |
||||
Project Name: CONSTRUCTING RETAINING WALL AND CONFINEMENT SYSTEM TO RESTORE SLIPOUT. |
||||
Prime Contractor: ARGONAUT CONSTRUCTION |
||||
Sample Taken Date: |
09/08/2023 |
Mix Design: |
72105003R |
|
Contractor: Unknown |
Location: SONOMA COUNTY NEAR JENNER FROM 0.3 MILE TO 0.7 MILE NORTH OF MEYERS GRADE ROAD |
|||
Structure unique identifier: 20-E0110 |
||||
Structure name: Slidesville Retaining Wall |
||||
Location of Pour: Waler25to29 |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C39 - Ground End
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 4.02 | 12.69 | 62367 | 4914.7 | 1 |
2 | 4.01 | 12.63 | 61658 | 4881.9 | 1 |
3 | 4.03 | 12.76 | 57415 | 4499.6 | 1 |
DIME Test ID: 2023-09-08-1-1
Number of specimens: 3
Compressive strength (to nearest 10 psi): 4770
Comment on any defect in either specimen or caps (Max 250 Characters):
Age of specimen: 7 days
Certified By: Spencer Adams
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 4.03 | 12.76 | 67895 | 5323.0 | 1 |
2 | 4.03 | 12.76 | 50351 | 3947.0 | 1 |
3 | 4.01 | 12.63 | 51468 | 4075 | 1 |
DIME Test ID: 2023-09-08-1-2
Number of specimens: 3
Compressive strength (to nearest 10 psi): 4450
Age of specimen: 10 days
Certified By: Spencer Adams
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 4.03 | 12.76 | 86413 | 6775.0 | 2 |
2 | 4.04 | 12.82 | 84164 | 6566.0 | 1 |
3 | 4.04 | 12.82 | 81142 | 6330 | 1 |
DIME Test ID: 2023-09-08-1-3
Number of specimens: 3
Compressive strength (to nearest 10 psi): 6560
Age of specimen: 28 days
Certified By: Spencer Adams
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing