Project Information

Project ID: 209139 DEA: 071170U4 EFIS: 0700000085 QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-10-33.2/37.2
Work Description: CONSTRUCT HOV LANES, WIDEN BRIDGES, AND REALIGN RAMPS.
Location Description: LOS ANGELES COUNTY IN BALDWIN PARK AND WEST COVINA FROM 0.1 MILE WEST OF PUENTE AVENUE UNDERCROSSING TO 0.2 MILE EAST OF HOLLENBECK STREET UNDERCROSSING
Contractor Name: Ames Construction, inc.
Contractor Address: 391 N Main Street, Suite 302, Corona, Ca 92880
Resident Engineer: Raj Punjabi Structure Rep.: Cardiel Bugarin

Sample Information

DIME Sample ID: 2016-02-25-3
TL Number from the TL Form: 101072109
Sample Submitted By Organization: CT - Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 02/25/2016
Date that the sample was received by the laboratory/organization performing the testing: 02/29/2016
The quantity of what the sample constitutes: 8
A brief description of the sample: 6X12
From where was the sample collected: Job Site
Laboratory sample identification: 882-09
Structure unique identifier: ROUTE I10
Structure name: VINCENT AVE UC ON RAMP DECK POUR
The fabricator/manufacturer/facility name: HOLLIDAY

Material Information

The concrete mix design number: CM5848
The truck number from where the sample was collected: 367
The batch plant ticket number from where the sample was collected: 101072019
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: truck
Where the material sample would have been placed if not sampled: Unknown
From Lot No.: Unknown
Bag Lot No.: Unknown

Test Results

Test 1 of 4

DIME Test ID: 2016-02-25-3-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Verified Date: 03/07/2016
Date Tested: 03/07/2016
Submitted By Organization: CT - Southern Regional Laboratory
Organization Address: 13970 Victoria St,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 213-792-4794
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.27 in^2
Capped in accordance with? ASTM C617/CTM521
Compressive strength (to nearest 10 psi) 4870 psi
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.00 in
Compressive strength of cylinder 1 5086.0 psi
Compressive strength of cylinder 2 4659.0 psi
Maximum load on cylinder 1 143780 lb
Maximum load on cylinder 2 131710 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 11 days

Test 2 of 4

DIME Test ID: 2016-02-25-3-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 03/10/2016
Date Tested: 03/10/2016
Submitted By Organization: CT - Southern Regional Laboratory
Organization Address: 13970 Victoria St,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 213-792-4794
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 5.99 in
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.18 in^2
Compressive strength (to nearest 10 psi) 4960 psi
Maximum load on cylinder 1 138190 lb
Maximum load on cylinder 2 141490 lb
Compressive strength of cylinder 1 4903.8 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 5020.9 psi
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 14 days
Age of specimen in hours no data

Test 3 of 4

DIME Test ID: 2016-02-25-3-3
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 03/24/2016
Date Tested: 03/24/2016
Submitted By Organization: CT - Southern Regional Laboratory
Organization Address: 13970 Victoria St,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 213-792-4794
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 5.98 in
Average diameter of cylinder 2 5.98 in
Cross sectional area of cylinder 1 28.09 in^2
Cross sectional area of cylinder 2 28.09 in^2
Compressive strength (to nearest 10 psi) 5530 psi
Maximum load on cylinder 1 157440 lb
Maximum load on cylinder 2 153300 lb
Compressive strength of cylinder 1 5604.8 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 5457.5 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 28 days
Age of specimen in hours no data

Test 4 of 4

DIME Test ID: 2016-02-25-3-4
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 04/08/2016
Date Tested: 04/07/2016
Submitted By Organization: CT - Southern Regional Laboratory
Organization Address: 13970 Victoria St,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 213-792-4794
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 5.98 in
Average diameter of cylinder 2 5.98 in
Cross sectional area of cylinder 1 28.09 in^2
Cross sectional area of cylinder 2 28.09 in^2
Compressive strength (to nearest 10 psi) 6270 psi
Maximum load on cylinder 1 179210 lb
Maximum load on cylinder 2 173030 lb
Compressive strength of cylinder 1 6379.9 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 6159.8 psi
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 42 days
Age of specimen in hours no data