Print Report | Back to Sample Detail

Sample Record for 2023-08-09-45

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 212112 DEA: 080C2514 EFIS: 0816000076 COOP: 081645 QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-10-0.0/13.2
Work Description: Design-Build of I-10 Corridor Contract 1 - Adding 2 new Express Lanes
Location Description: LA/SBD County Line to PM 13.2 near I-15
Contractor Name: Lane-Security Paving Joint Venture
Contractor Address: 3450 Centre Lake Drive, 1st Floor, Ontario, CA 91761
Resident Engineer: Jose Corona Structure Rep.: Luis Negrete

Sample Information

DIME Sample ID: 2023-08-09-45
TL Number from the TL Form: 1
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 08/09/2023
Date that the sample was received by the laboratory/organization performing the testing: 08/10/2023
The quantity of what the sample constitutes: 8
A brief description of the sample: Concrete Cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 1015-080
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Lane Security Joint Venture

Material Information

The concrete mix design number: 1610887
The truck number from where the sample was collected: 10067783
The batch plant ticket number from where the sample was collected: 30872285
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Monte Vista Ave UC Stage 2B Deck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 4

DIME Test ID: 2023-08-09-45-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/16/2023
Date Tested: 08/16/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? no data
Apparent mass of submerged cylinder 1 0 lb
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.00 in
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.27 in^2
Compressive strength (to nearest 10 psi) 4080 psi
Maximum load on cylinder 1 116655 lb
Maximum load on cylinder 2 113570 lb
Compressive strength of cylinder 1 4130.0 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 4020.0 psi
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1.00
Correction factor for cylinder 2 1.00
Age of specimen 7 days
Age of specimen in hours 0 hours
Serial number of delivery ticket, if available no data

Test 2 of 4

DIME Test ID: 2023-08-09-45-2
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/30/2023
Date Tested: 08/23/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? no data
Apparent mass of submerged cylinder 1 1 lb
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.01 in
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.37 in^2
Compressive strength (to nearest 10 psi) 4800 psi
Maximum load on cylinder 1 137450 lb
Maximum load on cylinder 2 134310 lb
Compressive strength of cylinder 1 4860.0 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 4730.0 psi
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1.00
Correction factor for cylinder 2 1.00
Age of specimen 14 days
Age of specimen in hours 0 hours
Serial number of delivery ticket, if available no data

Test 3 of 4

DIME Test ID: 2023-08-09-45-3
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/11/2023
Date Tested: 09/05/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? no data
Apparent mass of submerged cylinder 1 0 lb
Average diameter of cylinder 1 5.98 in
Average diameter of cylinder 2 5.99 in
Cross sectional area of cylinder 1 28.09 in^2
Cross sectional area of cylinder 2 28.18 in^2
Compressive strength (to nearest 10 psi) 4910 psi
Maximum load on cylinder 1 138530 lb
Maximum load on cylinder 2 137620 lb
Compressive strength of cylinder 1 4930.0 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 4880.0 psi
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1.00
Correction factor for cylinder 2 1.00
Age of specimen 28 days
Age of specimen in hours 0 hours
Serial number of delivery ticket, if available no data

Test 4 of 4

DIME Test ID: 2023-08-09-45-4
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/20/2023
Date Tested: 09/20/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? no data
Apparent mass of submerged cylinder 1 0 lb
Average diameter of cylinder 1 5.98 in
Average diameter of cylinder 2 5.99 in
Cross sectional area of cylinder 1 28.09 in^2
Cross sectional area of cylinder 2 28.18 in^2
Compressive strength (to nearest 10 psi) 5410 psi
Maximum load on cylinder 1 153880 lb
Maximum load on cylinder 2 150135 lb
Compressive strength of cylinder 1 5480.0 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 5330.0 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1.00
Correction factor for cylinder 2 1.00
Age of specimen 42 days
Age of specimen in hours 0 hours
Serial number of delivery ticket, if available no data