Sample Record for 2023-06-17-9

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 994675 DEA: 07390204 EFIS: 0722000334 QA Service Level: 1
DIST-CO-RTE-PM: 07---
Work Description:
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2023-06-17-9
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Informational
Type of Material: Concrete Core
Sample Taken Date: 06/17/2023
Date that the sample was received by the laboratory/organization performing the testing: 06/17/2023
The quantity of what the sample constitutes: 1
A brief description of the sample: Deck Core
From where was the sample collected: Job Site
Laboratory sample identification: Core 1
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Vincent Thomas Bridge

Material Information

Detail description: Core 1
Structure names: Vincent Thomas Bridge
Type of material: Concrete Core

Test Results

Test 1 of 2

DIME Test ID: 2023-06-17-9-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 08/14/2023
Date Tested: 07/10/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 1
Test performed With no density determined
Apparent mass of submerged cylinder 1 0 lb
Average diameter of cylinder 1 3.67 in
Cross sectional area of cylinder 1 10.58 in^2
Compressive strength of cylinder (to nearest 10 psi) 2800 psi
Maximum load on cylinder 1 32560 lb
Type of fracture pattern of cylinder 1 2
Comment on any defect in either specimen or caps (Max 250 Characters) SAMPLE TESTED AFTER SUBJECTED TO ASTM C642
Correction factor for cylinder 1 0.91
Age of specimen 0 days
Age of specimen in hours 0 hours
Serial number of delivery ticket, if available no data

Test 2 of 2

DIME Test ID: 2023-06-17-9-2
Test Method: ASTM C642-21: Standard Test Method for Density, Absorption, and Voids in Hardened Concrete
Verified Date: 09/25/2023
Date Tested: 07/06/2023
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Type of Specimen Core
Mass of over dried sample in air 2047.4 g
Mass of surface-dry sample in air after immersion 2237.8 g
Mass of surface-dry sample in air after immersion and boiling 2301.0 g
Apparent mass of sample in water after immersion and boiling 1037.8 g
Density of water 1.0 Mg/m^3
Absorption after immersion 9.3 %
Absorption after immersion and boiling 12.4 %
Bulk density, dry 1.6 Mg/m^3
Bulk density after immersion 1.8 Mg/m^3
Bulk density after immersion and boiling 1.8 Mg/m^3
Apparent density 2.0 Mg/m^3
Volume of permeable pore space 20.1 %