Project ID: 993868 DEA: 050C7324 EFIS: 0512000228
QA Service Level: 1
DIST-CO-RTE-PM: 05-SCR-1-13.4/14.9
Work Description: CONSTRUCT PEDESTRIAN OVERCROSSING AND AUXILIARY LANE.
Location Description: SANTA CRUZ COUNTY IN AND NEAR CITY OF CAPITOLA FROM 0.2 MILE SOUTH OF 41ST AVENUE OVERCROSSING TO 0.2 MILE NORTH OF SOQUEL DRIVE OVERCROSSING
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 585 BEACH STREET, WATSONVILLE CA 95076
Resident Engineer: Gareth Gill Structure Rep.: Chris McDermott
DIME Sample ID: 2023-06-27-37
TL Number from the TL Form:
Sample Submitted By Organization: Universal Precast Concrete - Redding
Sample Organization Contact: (530) 243-6477
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 06/27/2023
Date that the sample was received by the laboratory/organization performing the testing: 06/27/2023
The quantity of what the sample constitutes: 8.00yds
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Precast Unlimited
The concrete mix design number: C85A4M6
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 32258
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-06-27-37-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 06/28/2023
Date Tested: 06/27/2023
Submitted By Organization: Universal Precast Concrete - Redding
Organization Address: 16538 Clear Creek Road,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: mikeb@universalprecast.com
Organization Phone: (530) 243-6477
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
DIME Test ID: 2023-06-27-37-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 06/28/2023
Date Tested: 06/27/2023
Submitted By Organization: Universal Precast Concrete - Redding
Organization Address: 16538 Clear Creek Road,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: mikeb@universalprecast.com
Organization Phone: (530) 243-6477
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
DIME Test ID: 2023-06-27-37-3
Test Method: ASTM C231-17a: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 06/28/2023
Date Tested: 06/27/2023
Submitted By Organization: Universal Precast Concrete - Redding
Organization Address: 16538 Clear Creek Road,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: mikeb@universalprecast.com
Organization Phone: (530) 243-6477
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
DIME Test ID: 2023-06-27-37-4
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/28/2023
Date Tested: 06/28/2023
Submitted By Organization: Universal Precast Concrete - Redding
Organization Address: 16538 Clear Creek Road,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: mikeb@universalprecast.com
Organization Phone: (530) 243-6477
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
1
|
Test performed
|
With no density determined
|
Apparent mass of submerged cylinder 1
|
8.5 lb
|
Average diameter of cylinder 1
|
4.00 in
|
Compressive strength of cylinder (to nearest 10 psi)
|
2080 psi
|
Maximum load on cylinder 1
|
26150 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Age of specimen
|
1 days
|
Age of specimen in hours
|
0 hours
|
Serial number of delivery ticket, if available
|
no data
|
DIME Test ID: 2023-06-27-37-5
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 07/05/2023
Date Tested: 07/05/2023
Submitted By Organization: Universal Precast Concrete - Redding
Organization Address: 16538 Clear Creek Road,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: mikeb@universalprecast.com
Organization Phone: (530) 243-6477
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Apparent mass of submerged cylinder 1
|
8.5 lb
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
4920 psi
|
Maximum load on cylinder 1
|
59960 lb
|
Maximum load on cylinder 2
|
63670 lb
|
Type of fracture pattern of cylinder 1
|
4
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Correction factor for cylinder 2
|
1.00
|
Age of specimen
|
8 days
|
Age of specimen in hours
|
0 hours
|
Serial number of delivery ticket, if available
|
no data
|
DIME Test ID: 2023-06-27-37-6
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 07/25/2023
Date Tested: 07/25/2023
Submitted By Organization: Universal Precast Concrete - Redding
Organization Address: 16538 Clear Creek Road,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: mikeb@universalprecast.com
Organization Phone: (530) 243-6477
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Apparent mass of submerged cylinder 1
|
8050 lb
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
6860 psi
|
Maximum load on cylinder 1
|
85850 lb
|
Maximum load on cylinder 2
|
86230 lb
|
Maximum load on cylinder 3
|
86730 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Type of fracture pattern of cylinder 2
|
3
|
Type of fracture pattern of cylinder 3
|
4
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Correction factor for cylinder 2
|
1.00
|
Correction factor for cylinder 3
|
1.00
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
0 hours
|
Serial number of delivery ticket, if available
|
no data
|