Sample Record for 2023-06-23-5

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 214135 DEA: 09213404 EFIS: 0900000030 QA Service Level: 1
DIST-CO-RTE-PM: 09-INY-395-29.9/41.8
Work Description: ROADWAY EXCAVATION, PLACE HMA (TYPE A), AND ALTERNATIVE PIPE CULVERT.
Location Description: INYO COUNTY NEAR OLANCHA AND CARTAGO FROM 1.4 MILES SOUTH OF LOS ANGELES AQUEDUCT BRIDGE TO 0.2 MILE SOUTH OF ASH CREEK BRIDGE
Contractor Name: FISHER SAND & GRAVEL CO.
Contractor Address: 1302 W DRIVERS WAY, TEPE, AZ. 85284
Resident Engineer: Kris Raber Structure Rep.: Alex Naime-Falcon

Sample Information

DIME Sample ID: 2023-06-23-5
TL Number from the TL Form:
Sample Submitted By Organization: CT D09 - Bishop Field Laboratory
Sample Organization Contact: (760) 872-5211
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 06/23/2023
Date that the sample was received by the laboratory/organization performing the testing: 06/23/2023
The quantity of what the sample constitutes: 1 bag
A brief description of the sample: DS 1343 RCB 1B Upper Deck
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: 711 Materials Ridgecrest

Material Information

The concrete mix design number: 750216A6
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: Concrete Plant
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: DS 1343 RCB 1B Upper Deck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 3

DIME Test ID: 2023-06-23-5-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 07/21/2023
Date Tested: 07/21/2023
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: Cylinders: 3 @ 28day
Test Result Compliance: does not comply
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 3320 psi
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Compressive strength of cylinder 1 3376.3 psi
Compressive strength of cylinder 2 3350.0 psi
Average diameter of cylinder 3 4.00 in
Compressive strength of cylinder 3 3237.9 psi
Maximum load on cylinder 1 42440 lb
Maximum load on cylinder 2 42110 lb
Maximum load on cylinder 3 40700 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 1
Type of fracture pattern of cylinder 3 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 28 days

Test 2 of 3

DIME Test ID: 2023-06-23-5-3
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 08/04/2023
Date Tested: 08/04/2023
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: Cylinders: 3 @ 42day 2 @ 56day
Test Result Compliance: does not comply
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 3750 psi
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Compressive strength of cylinder 1 3653.1 psi
Compressive strength of cylinder 2 3874.3 psi
Average diameter of cylinder 3 4.00 in
Compressive strength of cylinder 3 3717.6 psi
Maximum load on cylinder 1 45920 lb
Maximum load on cylinder 2 48700 lb
Maximum load on cylinder 3 46730 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 1
Type of fracture pattern of cylinder 3 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 42 days

Test 3 of 3

DIME Test ID: 2023-06-23-5-4
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 08/18/2023
Date Tested: 08/18/2023
Submitted By Organization: CT D09 - Bishop Field Laboratory
Organization Address: 500 South Main Street,
Organization City: Bishop
Organization State: CA
Organization Zipcode: 93514
Organization Email: chris.talbot@dot.ca.gov
Organization Phone: (760) 872-0794
General Comments for this Test: 3 @ 56day
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 4140 psi
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Compressive strength of cylinder 1 4031.8 psi
Compressive strength of cylinder 2 4254.2 psi
Average diameter of cylinder 3 4.00 in
Compressive strength of cylinder 3 4132.5 psi
Maximum load on cylinder 1 50680 lb
Maximum load on cylinder 2 53475 lb
Maximum load on cylinder 3 51945 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 1
Type of fracture pattern of cylinder 3 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 56 days