Sample Record for 2023-05-24-68
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 209820 DEA: 04297634 EFIS: 0415000040 COOP: 042548
QA Service Level: 1
DIST-CO-RTE-PM: 04-ALA-84,680-17.9/21
Work Description: ROUTE 84 WIDENING (4-LANE EXPRESSWAY) FROM I-680 TO PIGEON PASS, INCLUDING INTERSECTION, DRAINAGE IMPROVEMENTS AND UTILITY RELOCATION.
Location Description: ALAMEDA COUNTY IN AND NEAR SUNOL, PLEASANTON, AND LIVERMORE ON ROUTE 84 FROM 0.1 MILE EAST OF ROUTE 680 TO 0.1 MILE SOUTH OF RUBY HILL DRIVE AND ON ROUTE 680 FROM 1.2 MILES SOUTH TO 1.8 MILES NORTH OF ROUTE 84
Contractor Name: Bay Cities Paving & Grading
Contractor Address: 1450 Civic Ct. BLDG B #400, Concord CA, 94520
Resident Engineer: Paramjit Pandher Structure Rep.: Kristen We
Sample Information
DIME Sample ID: 2023-05-24-68
TL Number from the TL Form:
Sample Submitted By Organization: Reinforced Earth Company
Sample Organization Contact: (760) 447-6746
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 05/24/2023
Date that the sample was received by the laboratory/organization performing the testing: 05/24/2023
The quantity of what the sample constitutes: 8 Cylinders
A brief description of the sample: ASTM
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Reinforced Earth Co
Material Information
The concrete mix design number: CT675F25
The truck number from where the sample was collected: 225
The batch plant ticket number from where the sample was collected: 811404
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: ORO GRANDE
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 6
DIME Test ID: 2023-05-24-68-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 06/22/2023
Date Tested: 05/24/2023
Submitted By Organization: Reinforced Earth Company
Organization Address: 17248 North D Street,
Organization City: Victorville
Organization State: CA
Organization Zipcode: 92394
Organization Email: rfisher@reinforcedearth.com
Organization Phone: (909) 273-1712
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Test 2 of 6
DIME Test ID: 2023-05-24-68-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 06/22/2023
Date Tested: 05/24/2023
Submitted By Organization: Reinforced Earth Company
Organization Address: 17248 North D Street,
Organization City: Victorville
Organization State: CA
Organization Zipcode: 92394
Organization Email: rfisher@reinforcedearth.com
Organization Phone: (909) 273-1712
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Test 3 of 6
DIME Test ID: 2023-05-24-68-3
Test Method: ASTM C231-17a: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 06/22/2023
Date Tested: 05/24/2023
Submitted By Organization: Reinforced Earth Company
Organization Address: 17248 North D Street,
Organization City: Victorville
Organization State: CA
Organization Zipcode: 92394
Organization Email: rfisher@reinforcedearth.com
Organization Phone: (909) 273-1712
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Test 4 of 6
DIME Test ID: 2023-05-24-68-4
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/22/2023
Date Tested: 05/31/2023
Submitted By Organization: Reinforced Earth Company
Organization Address: 17248 North D Street,
Organization City: Victorville
Organization State: CA
Organization Zipcode: 92394
Organization Email: rfisher@reinforcedearth.com
Organization Phone: (909) 273-1712
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.01 in
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Compressive strength (to nearest 10 psi)
|
3880 psi
|
Maximum load on cylinder 1
|
111580 lb
|
Maximum load on cylinder 2
|
108530 lb
|
Type of fracture pattern of cylinder 1
|
5
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
7 days
|
Age of specimen in hours
|
no data0 hours
|
Serial number of delivery ticket, if available
|
no data
|
Test 5 of 6
DIME Test ID: 2023-05-24-68-5
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/22/2023
Date Tested: 06/07/2023
Submitted By Organization: Reinforced Earth Company
Organization Address: 17248 North D Street,
Organization City: Victorville
Organization State: CA
Organization Zipcode: 92394
Organization Email: rfisher@reinforcedearth.com
Organization Phone: (909) 273-1712
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.01 in
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Compressive strength (to nearest 10 psi)
|
4390 psi
|
Maximum load on cylinder 1
|
125200 lb
|
Maximum load on cylinder 2
|
124070 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Type of fracture pattern of cylinder 2
|
5
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
14 days
|
Age of specimen in hours
|
no data0 hours
|
Serial number of delivery ticket, if available
|
no data
|
Test 6 of 6
DIME Test ID: 2023-05-24-68-6
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/22/2023
Date Tested: 06/21/2023
Submitted By Organization: Reinforced Earth Company
Organization Address: 17248 North D Street,
Organization City: Victorville
Organization State: CA
Organization Zipcode: 92394
Organization Email: rfisher@reinforcedearth.com
Organization Phone: (909) 273-1712
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
no data0 lb
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.01 in
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Compressive strength (to nearest 10 psi)
|
4950 psi
|
Maximum load on cylinder 1
|
141880 lb
|
Maximum load on cylinder 2
|
138970 lb
|
Type of fracture pattern of cylinder 1
|
5
|
Type of fracture pattern of cylinder 2
|
5
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
no data0 hours
|
Serial number of delivery ticket, if available
|
no data
|