Print Report | Back to Sample Detail

Sample Record for 2015-11-19-9

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 208714 DEA: 08043514 EFIS: 0800000010 QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-58-R22.2/R31.1
Work Description: REALIGN AND WIDEN 2 TO 4 LANES EXPRESSWAY
Location Description: HINKLEY ROAD FROM 2.4 MILES WEST OF HIDDEN RIVER ROAD TO? 0.7 MILE EAST OF LENWOOD ROAD.
Contractor Name: Skanska Civil USA
Contractor Address: 1995 Agua Mansa Road, Riverside, CA 92509
Resident Engineer: Shaine Shahidi Structure Rep.: Ahmad Ankir

Sample Information

DIME Sample ID: 2015-11-19-9
TL Number from the TL Form: P23A
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 11/19/2015
Date that the sample was received by the laboratory/organization performing the testing: 11/24/2015
The quantity of what the sample constitutes: 8
A brief description of the sample: 6X12
From where was the sample collected: Job Site
Laboratory sample identification: 915-3A
Structure unique identifier: CONST SBC AT HINKLEY RD
Structure name: OC BR DECK
The fabricator/manufacturer/facility name: ROBERTSONS

Material Information

The concrete mix design number: SC675B38
The truck number from where the sample was collected: NP
The batch plant ticket number from where the sample was collected: NP
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: LOAD 31
Where the material sample would have been placed if not sampled: Unknown
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 4

DIME Test ID: 2015-11-19-9-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/30/2015
Date Tested: 11/26/2015
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 5.98 in
Average diameter of cylinder 2 5.98 in
Cross sectional area of cylinder 1 28.09 in^2
Cross sectional area of cylinder 2 28.09 in^2
Compressive strength (to nearest 10 psi) 4280 psi
Maximum load on cylinder 1 121830 lb
Maximum load on cylinder 2 118560 lb
Compressive strength of cylinder 1 4337.1 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 4220.7 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 7 days
Age of specimen in hours no data

Test 2 of 4

DIME Test ID: 2015-11-19-9-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/30/2015
Date Tested: 11/30/2015
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 5.99 in
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.18 in^2
Compressive strength (to nearest 10 psi) 4510 psi
Maximum load on cylinder 1 126160 lb
Maximum load on cylinder 2 128090 lb
Compressive strength of cylinder 1 4476.9 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 4545.4 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 11 days
Age of specimen in hours no data

Test 3 of 4

DIME Test ID: 2015-11-19-9-3
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 12/03/2015
Date Tested: 12/03/2015
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 5.99 in
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.18 in^2
Compressive strength (to nearest 10 psi) 4690 psi
Maximum load on cylinder 1 132770 lb
Maximum load on cylinder 2 131380 lb
Compressive strength of cylinder 1 4711.5 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 4662.2 psi
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 14 days
Age of specimen in hours no data

Test 4 of 4

DIME Test ID: 2015-11-19-9-4
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 12/17/2015
Date Tested: 12/17/2015
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617/CTM521
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 5.99 in
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.18 in^2
Compressive strength (to nearest 10 psi) 5540 psi
Maximum load on cylinder 1 156740 lb
Maximum load on cylinder 2 155710 lb
Compressive strength of cylinder 1 5562.1 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 5525.6 psi
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 no data
Age of specimen 28 days
Age of specimen in hours no data