Project Information

Project ID: 994062 DEA: 010F5104 EFIS: 0116000015 QA Service Level: 1
DIST-CO-RTE-PM: 01-MEN,HUM-101-R106.2/T106.8
Work Description: SOUTH FORK EEL RIVER BRIDGE SEISMIC
Location Description: MENDOCINO AND HUMBOLDT COUNTIES NEAR COOKS VALLEY FROM 0.4 MILE SOUTH OF SOUTH FORK EEL RIVER BRIDGE TO 0.1 MILE NORTH OF ROUTE 271
Contractor Name: J.F. SHEA CONSTRUCTION, INC.
Contractor Address: 667 BREA CANYON ROAD, SUITE 3, WALNUT CA 91789
Resident Engineer: Joaquin Rodriguez Structure Rep.: George Moore

Sample Information

DIME Sample ID: 2023-05-16-19
TL Number from the TL Form:
Sample Submitted By Organization: CT D01 - District 1 Materials Laboratory
Sample Organization Contact: (707) 496-0974
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 05/16/2023
Date that the sample was received by the laboratory/organization performing the testing: 05/17/2023
The quantity of what the sample constitutes: 2 - 6x12 cylinders
A brief description of the sample: PCC cylinders
From where was the sample collected: Job Site
Laboratory sample identification: C0154
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Mercer Fraser - Fortuna

Material Information

The concrete mix design number: none
The truck number from where the sample was collected: 3402
The batch plant ticket number from where the sample was collected: none
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 1

DIME Test ID: 2023-05-16-19-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 06/27/2023
Date Tested: 06/27/2023
Submitted By Organization: CT D01 - District 1 Materials Laboratory
Organization Address: 1726 Albee Street,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: leif.ayres@dot.ca.gov
Organization Phone: (707) 496-0974
General Comments for this Test: 42 day test
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.00 in
Cross sectional area of cylinder 1 28.3 in^2
Cross sectional area of cylinder 2 28.3 in^2
Compressive strength (to nearest 10 psi) 7060 psi
Maximum load on cylinder 1 202410 lb
Maximum load on cylinder 2 196750 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 42 days
Age of specimen in hours 0 hours