Sample Record for 2015-10-19-5
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 209139 DEA: 071170U4 EFIS: 0700000085
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-10-33.2/37.2
Work Description: CONSTRUCT HOV LANES, WIDEN BRIDGES, AND REALIGN RAMPS.
Location Description: LOS ANGELES COUNTY IN BALDWIN PARK AND WEST COVINA FROM 0.1 MILE WEST OF PUENTE AVENUE UNDERCROSSING TO 0.2 MILE EAST OF HOLLENBECK STREET UNDERCROSSING
Contractor Name: Ames Construction, inc.
Contractor Address: 391 N Main Street, Suite 302, Corona, Ca 92880
Resident Engineer: Raj Punjabi Structure Rep.: Cardiel Bugarin
Sample Information
DIME Sample ID: 2015-10-19-5
TL Number from the TL Form: 101061878
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 10/19/2015
Date that the sample was received by the laboratory/organization performing the testing: 10/20/2015
The quantity of what the sample constitutes: 6
A brief description of the sample: 6X12
From where was the sample collected: Job Site
Laboratory sample identification: 882-78
Structure unique identifier: I10 LARK ELLEN AVE UC
Structure name: ALL ABUT END DIAPHRAGMS LEFT AND RIGHT
The fabricator/manufacturer/facility name: HOLLIDAY
Material Information
The concrete mix design number: CM5856
The truck number from where the sample was collected: 361
The batch plant ticket number from where the sample was collected: 101061878
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: TRUCK
Where the material sample would have been placed if not sampled: Unknown
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 3
DIME Test ID: 2015-10-19-5-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/02/2015
Date Tested: 11/02/2015
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.01 in
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Compressive strength (to nearest 10 psi)
|
5230 psi
|
Maximum load on cylinder 1
|
143900 lb
|
Maximum load on cylinder 2
|
152860 lb
|
Compressive strength of cylinder 1
|
5072.3 psi
|
Type of fracture pattern of cylinder 1
|
2
|
Compressive strength of cylinder 2
|
5388.1 psi
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
14 days
|
Age of specimen in hours
|
no data
|
Test 2 of 3
DIME Test ID: 2015-10-19-5-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/16/2015
Date Tested: 11/16/2015
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With density determined by dimension measurements
|
Average cylinder density (to nearest 1 pcf)
|
822277 lb/ft^3
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.01 in
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Test 3 of 3
DIME Test ID: 2015-10-19-5-3
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/30/2015
Date Tested: 11/30/2015
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.01 in
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Compressive strength (to nearest 10 psi)
|
6230 psi
|
Maximum load on cylinder 1
|
183520 lb
|
Maximum load on cylinder 2
|
169710 lb
|
Compressive strength of cylinder 1
|
6468.8 psi
|
Type of fracture pattern of cylinder 1
|
3
|
Compressive strength of cylinder 2
|
5982.0 psi
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
42 days
|
Age of specimen in hours
|
no data
|