Print Report | Back to Sample Detail

Sample Record for 2023-04-18-107

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215649 DEA: 043G4884 EFIS: 0412000088 QA Service Level: 1
DIST-CO-RTE-PM: 04-SM-92-R14.4/R18.8
Work Description: CLEAN AND PAINT STEEL BRIDGE TOWERS, REPLACE HIGH STRENGTH BOLTS.
Location Description: SAN MATEO COUNTY IN FOSTER CITY FROM SAN MATEO-HAYWARD BRIDGE TO ALAMEDA COUNTY LINE
Contractor Name: Cekra, Inc. (Nash Hale)
Contractor Address: PO Box 7964, Wilmington, NC 28406
Resident Engineer: Kingston Atako Structure Rep.: Stanley Ku

Sample Information

DIME Sample ID: 2023-04-18-107
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Per Request
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 04/18/2023
Date that the sample was received by the laboratory/organization performing the testing: 04/20/2023
The quantity of what the sample constitutes: 3
A brief description of the sample: Bolts
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Pier 27 North

Material Information

Rocap Number(s):
Heat Number(s): NA
Nut Mfg. Lot Number(s):
Washer Mfg. Lot Number(s):
Bolt Specification: A325
Bolt Length(s): 4, 4.5, 4.5
Nut Specification: NA
Washer Specification: NA
Finish: NA
Diameter/Size: 0.875
Bolt Mfg. Lot Number: NA
Rocap Test Requirement(s):
Lubricant Requirements(s):

Test Results

Test 1 of 3

DIME Test ID: 2023-04-18-107-1
Test Method: ASTM F606-21: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Proof Load with Wedge)
Verified Date: 05/16/2023
Date Tested: 05/16/2023
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: A325 wedge tensile Pier 27 N
Test Result Compliance:
Additional Comments When Verified:
Number of Bolt Samples 1
SampleBolt Mfg. Lot NumberSize (in)Peak Load (lbf)Peak Load (kN)Wedge Angle (deg)CommentsTested By
1ANA0.87506407128510.00A325 wedge tensile Pier 27 Nrmacias
UTM 450kip
Temperature no data

Test 2 of 3

DIME Test ID: 2023-04-18-107-2
Test Method: ASTM F606-21: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Proof Load with Wedge)
Verified Date: 05/16/2023
Date Tested: 05/16/2023
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: A325 wedge tensile Pier 27 N
Test Result Compliance:
Additional Comments When Verified:
Number of Bolt Samples 1
SampleBolt Mfg. Lot NumberSize (in)Peak Load (lbf)Peak Load (kN)Wedge Angle (deg)CommentsTested By
2ANA0.875064131285.2710.00A325 wedge tensile Pier 27 Nrmacias
UTM 450kip
Temperature no data

Test 3 of 3

DIME Test ID: 2023-04-18-107-3
Test Method: ASTM F606-21: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Proof Load with Wedge)
Verified Date: 05/16/2023
Date Tested: 05/16/2023
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: A325 wedge tensile Pier 27 N
Test Result Compliance:
Additional Comments When Verified:
Number of Bolt Samples 1
SampleBolt Mfg. Lot NumberSize (in)Peak Load (lbf)Peak Load (kN)Wedge Angle (deg)CommentsTested By
3ANA0.875063835283.9510.00A325 wedge tensile Pier 27 Nrmacias
UTM 450kip
Temperature no data