Sample Information

DIME Sample ID: 2023-04-28-49
TL Number from the TL Form:
Sample Submitted By Organization: CT D01 - Fort Bragg Field Laboratory
Sample Organization Contact: (707) 496-0974
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 04/28/2023
Date that the sample was received by the laboratory/organization performing the testing: 04/28/2023
The quantity of what the sample constitutes: 16 Cy
A brief description of the sample: 7.2 Sk Structural (Corrosive)
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 10-0158
Structure name: Pudding Creek Bridge
The fabricator/manufacturer/facility name: geoaggregates

Material Information

The concrete mix design number: 7-Sk-Structual
The truck number from where the sample was collected: 09
The batch plant ticket number from where the sample was collected: 24241
Concrete batch plant: Geoaggregates
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 1

DIME Test ID: 2023-04-28-49-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 05/11/2023
Date Tested: 05/05/2023
Submitted By Organization: CT D01 - Fort Bragg Field Laboratory
Organization Address: 1726 Albee Street,
Organization City: Eureka
Organization State: CA
Organization Zipcode: 95501
Organization Email: leif.ayres@dot.ca.gov
Organization Phone: (707) 496-0974
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Average diameter of cylinder 3 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Cross sectional area of cylinder 3 12.57 in^2
Compressive strength (to nearest 10 psi) 3120 psi
Maximum load on cylinder 1 39620 lb
Maximum load on cylinder 2 39480 lb
Maximum load on cylinder 3 38420 lb
Compressive strength of cylinder 1 3151.9 psi
Type of fracture pattern of cylinder 1 1
Compressive strength of cylinder 2 3140.8 psi
Compressive strength of cylinder 3 3056.5 psi
Type of fracture pattern of cylinder 2 1
Type of fracture pattern of cylinder 3 1
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 3 days
Age of specimen in hours 0 hours