Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 7613 DEA: 071218W4 EFIS: 0700021119
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-5-29.4/31.6
Work Description: REALIGN ROUTE 5 AND RAILROAD TRACKS AND RECONFIGURE ON- AND OFF-RAMPS.
Location Description: LOS ANGELES COUNTY IN BURBANK FROM WEST MAGNOLIA BOULEVARD OVERCROSSING TO 0.3 MILE NORTH OF BUENA VISTA STREET/WINONA AVENUE UNDERCROSSING
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 13170 TELFAIR AVENUE, SYLMAR, CA 91342
Resident Engineer: Vladimir Gurfinkel Structure Rep.: Gon Choi
DIME Sample ID: 2015-10-07-6
TL Number from the TL Form: 1007
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 10/07/2015
Date that the sample was received by the laboratory/organization performing the testing: 10/13/2015
The quantity of what the sample constitutes: 2
A brief description of the sample: 6X12
From where was the sample collected: Job Site
Laboratory sample identification: 889-07
Structure unique identifier: CIDH PILES AT VICTORY PLACE BR 53C2171
Structure name: CIDH PILES AT ABUT1 BENT2 ABUT3 BR 53C2171
The fabricator/manufacturer/facility name: CEMEX
The concrete mix design number: 1570340
The truck number from where the sample was collected: 7029
The batch plant ticket number from where the sample was collected: 26139375
Concrete batch plant: Unknown
The fabricator/manufacturer designation for the sample: Unknown
A detailed description of where the material sample was collected: SHUTE
Where the material sample would have been placed if not sampled: Unknown
From Lot No.:
Bag Lot No.:
DIME Test ID: 2015-10-07-6-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 11/04/2015
Date Tested: 11/04/2015
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: (909) 829-3029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617/CTM521
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Compressive strength (to nearest 10 psi)
|
4610 psi
|
Maximum load on cylinder 1
|
130760 lb
|
Maximum load on cylinder 2
|
130000 lb
|
Compressive strength of cylinder 1
|
4625.4 psi
|
Type of fracture pattern of cylinder 1
|
3
|
Compressive strength of cylinder 2
|
4598.5 psi
|
Type of fracture pattern of cylinder 2
|
1
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
no data
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
no data
|