Print Report | Back to Sample Detail

Sample Record for 2023-04-26-12

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 993253 DEA: 033F0604 EFIS: 0312000052 QA Service Level: 1
DIST-CO-RTE-PM: 03-GLE-162-76.3/78.6
Work Description:
Location Description:
Contractor Name: GOLDEN STATE BRIDGE
Contractor Address: 3701 Mallard Drive, Benicia, CA 94510
Resident Engineer: Anthony Granados Structure Rep.: Matt Crete

Sample Information

DIME Sample ID: 2023-04-26-12
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Sacramento Field Office
Sample Organization Contact: (916) 2058871
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 04/26/2023
Date that the sample was received by the laboratory/organization performing the testing: 04/27/2023
The quantity of what the sample constitutes: 570 Heads
A brief description of the sample: Dual Headed #9 Bars
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: CMC Rebar Fresno

Material Information

Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 6037588
Head Manufacturer Lot Number(s): NA
Rebar Size: #9
Headed Bar Model Name: HRC 555
Size of Head: Reduced Size - 4x
Head Connection Type: Forged
Head Shape: Circular
Rebar Manufacturer: CMC Steel Oklahoma
Head Manufacturer: NA
Head Fabricator: CMC Rebar Fresno
Material Standard Code: ASTM A706
Headed Bar Unique ID: 4FG-17-01

Test Results

Test 1 of 3

DIME Test ID: 2023-04-26-12-1
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/28/2023
Date Tested: 04/27/2023
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
51101982101982Ok Neckingrmacias
Temperature 72 f
UTM 400kip

Test 2 of 3

DIME Test ID: 2023-04-26-12-2
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/28/2023
Date Tested: 04/27/2023
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
51101426101426Ok Neckingrmacias
Temperature 72 f
UTM 400kip

Test 3 of 3

DIME Test ID: 2023-04-26-12-3
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/28/2023
Date Tested: 04/27/2023
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Ok Necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
519986299862Ok Neckingrmacias
Temperature 72 f
UTM 400kip