Sample Record for 2023-03-09-36

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215129 DEA: 050N73U4 EFIS: 0520000166 QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-7.3/9.6
Work Description: !!Please CC Office Engineer Gabrielle Herrera on reports to RE and SR!! Segment 4C - Summerland: Construct HOV lanes and rehabilitation. Source inspection of sign structure trusses, lighting structures, steel soldier piles, epoxy coated rebar,
Location Description: SUMMERLAND FROM 0.2 MILES NORTH OF PARDARO LANE OVERCROSSING TO SAN YSIDRO CREEK BRIDGE
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: PO Box 6744, Santa Barbara , CA 93111
Resident Engineer: Luobao Cai Structure Rep.: Emiliano Berntsen

Sample Information

DIME Sample ID: 2023-03-09-36
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Sample Organization Contact: (805) 621-3616
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 03/09/2023
Date that the sample was received by the laboratory/organization performing the testing: 03/09/2023
The quantity of what the sample constitutes: 19 cy
A brief description of the sample: Concrete Sample
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Martin Marietta Goleta

Material Information

The concrete mix design number: 63511N0P
The truck number from where the sample was collected: 516
The batch plant ticket number from where the sample was collected: 3433070
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 3

DIME Test ID: 2023-03-09-36-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 03/20/2023
Date Tested: 03/09/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Temperature 71 F

Test 2 of 3

DIME Test ID: 2023-03-09-36-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 03/20/2023
Date Tested: 03/09/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Slump 5.25 inch

Test 3 of 3

DIME Test ID: 2023-03-09-36-3
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 07/18/2023
Date Tested: 03/09/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Apparent mass of submerged cylinder 1 0 lb
Average diameter of cylinder 1 4.01 in
Average diameter of cylinder 2 4.03 in
Average diameter of cylinder 3 4.02 in
Cross sectional area of cylinder 1 12.63 in^2
Cross sectional area of cylinder 2 12.76 in^2
Cross sectional area of cylinder 3 12.69 in^2
Compressive strength (to nearest 10 psi) 7410 psi
Maximum load on cylinder 1 95320 lb
Maximum load on cylinder 2 96210 lb
Maximum load on cylinder 3 90640 lb
Compressive strength of cylinder 1 7550.0 psi
Type of fracture pattern of cylinder 1 5
Compressive strength of cylinder 2 7540.0 psi
Compressive strength of cylinder 3 7140 psi
Type of fracture pattern of cylinder 2 5
Type of fracture pattern of cylinder 3 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1.00
Correction factor for cylinder 2 1.00
Correction factor for cylinder 3 1.00
Age of specimen 28 days
Age of specimen in hours 0 hours
Serial number of delivery ticket, if available no data