Sample Record for 2023-03-08-55

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 994087 DEA: 051G4104 EFIS: 0515000012 QA Service Level: 1
DIST-CO-RTE-PM: 05-SB-101-4.0/4.8
Work Description: Santa Claus Lane Bike Path - !!Charge time to 05-0N72U4 per Project Manager / Corridor Manager!!
Location Description: !!Charge time to 05-0N72U4 per Project Manager / Corridor Manager!!
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 5335 Debbie Road, Santa Barbara, CA 93111
Resident Engineer: Luobao Cai Structure Rep.: Josh Madrigal

Sample Information

DIME Sample ID: 2023-03-08-55
TL Number from the TL Form:
Sample Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Sample Organization Contact: (805) 621-3616
Type of Sample: Department Acceptance
Type of Material: Concrete
Sample Taken Date: 03/08/2023
Date that the sample was received by the laboratory/organization performing the testing: 03/08/2023
The quantity of what the sample constitutes: 38 CY
A brief description of the sample: Concrete Sample
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Martin Marietta Goleta

Material Information

The concrete mix design number: 725A1Z0P
The truck number from where the sample was collected: 544
The batch plant ticket number from where the sample was collected: 3433048
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 3

DIME Test ID: 2023-03-08-55-1
Test Method: ASTM C1064-17: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Verified Date: 03/20/2023
Date Tested: 03/08/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Temperature 69 F

Test 2 of 3

DIME Test ID: 2023-03-08-55-2
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 03/20/2023
Date Tested: 03/08/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Slump 4 inch

Test 3 of 3

DIME Test ID: 2023-03-08-55-3
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 07/17/2023
Date Tested: 04/05/2023
Submitted By Organization: CT D05 - Carpinteria Field Laboratory
Organization Address: 21 Griffin Road North,
Organization City: Windsor
Organization State: CT
Organization Zipcode: 06095-1590
Organization Email: dlachaine@trccompanies.com
Organization Phone: (805) 621-3616
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Apparent mass of submerged cylinder 1 0 lb
Average diameter of cylinder 1 4.02 in
Average diameter of cylinder 2 4.02 in
Average diameter of cylinder 3 4.02 in
Cross sectional area of cylinder 1 12.69 in^2
Cross sectional area of cylinder 2 12.69 in^2
Cross sectional area of cylinder 3 12.69 in^2
Compressive strength (to nearest 10 psi) 6250 psi
Maximum load on cylinder 1 79270 lb
Maximum load on cylinder 2 82640 lb
Maximum load on cylinder 3 75830 lb
Compressive strength of cylinder 1 6250.0 psi
Type of fracture pattern of cylinder 1 3
Compressive strength of cylinder 2 6510.0 psi
Compressive strength of cylinder 3 5980 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1.00
Correction factor for cylinder 2 1.00
Correction factor for cylinder 3 1.00
Age of specimen 28 days
Age of specimen in hours 0 hours
Serial number of delivery ticket, if available no data