Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 215788 DEA: 101C7904 EFIS: 1016000046
QA Service Level: 1
DIST-CO-RTE-PM: 10-MER-5-0.4
Work Description: BUILDING WORK.
Location Description: MERCED COUNTY 0.4 MILE NORTH OF THE FRESNO COUNTY LINE AT THE JOHN "CHUCK" ERRECA SAFETY ROADSIDE REST AREA
Contractor Name: Walsh Construction Company II, LLC (Walsh) - Bryce Frederick
Contractor Address: 1390 Willow Pass Road Suite 950, Concord, CA 94520
Resident Engineer: Zubair Anwar Structure Rep.: Ramandeep "Raman" Guraya
DIME Sample ID: 2023-01-30-61
TL Number from the TL Form:
Sample Submitted By Organization: CT D06 - Millbrook Field Laboratory
Sample Organization Contact: (559) 417-5341
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 01/30/2023
Date that the sample was received by the laboratory/organization performing the testing: 01/31/2023
The quantity of what the sample constitutes: 300 cy
A brief description of the sample: structural concrete
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name: NB SB picnic slab
The fabricator/manufacturer/facility name: Unknown
The concrete mix design number: S193
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: Unknown
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2023-01-30-61-1
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 02/27/2023
Date Tested: 02/27/2023
Submitted By Organization: CT D06 - Millbrook Field Laboratory
Organization Address: 3240 North Millbrook Avenue,
Organization City: Fresno
Organization State: CA
Organization Zipcode: 93726
Organization Email: tomas.silva@dot.ca.gov
Organization Phone: (559) 417-5341
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Average diameter of cylinder 1
|
4.01 in
|
Average diameter of cylinder 2
|
4.01 in
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Average diameter of cylinder 3
|
4.02 in
|
Cross sectional area of cylinder 1
|
12.63 in^2
|
Cross sectional area of cylinder 2
|
12.63 in^2
|
Cross sectional area of cylinder 3
|
12.69 in^2
|
Compressive strength (to nearest 10 psi)
|
5930 psi
|
Maximum load on cylinder 1
|
67070 lb
|
Maximum load on cylinder 2
|
79670 lb
|
Maximum load on cylinder 3
|
78280 lb
|
Compressive strength of cylinder 1
|
5310.4 psi
|
Type of fracture pattern of cylinder 1
|
3
|
Compressive strength of cylinder 2
|
6308.0 psi
|
Compressive strength of cylinder 3
|
6168.6 psi
|
Type of fracture pattern of cylinder 2
|
3
|
Type of fracture pattern of cylinder 3
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
27 days
|
Age of specimen in hours
|
0 hours
|