Sample Record for 2022-12-22-30
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 993333 DEA: 04264724 EFIS: 0419000068
QA Service Level: 1
DIST-CO-RTE-PM: 04-MRN-101-R20.8/27.1
Work Description: CIP BRIDGES, CONSTRUCT ROADWAY, RETAINING WALLS AND MODIFY ELECTRICAL.
Location Description: MARIN COUNTY IN AND NEAR NOVATO FROM 0.1 MILE SOUTH OF FRANKLIN AVENUE OVERHEAD TO 0.5 MILE SOUTH OF SAN ANTONIO CREEK BRIDGE
Contractor Name: GHILOTTI CONSTRUCTION CO. INC. (RILEY GENAZZI & JOSH SERAFINO)
Contractor Address: 246 GHILOTTI AVE., SANTA ROSA, CA 95407
Resident Engineer: Fabio La Serna Structure Rep.: Jeremy Light
Sample Information
DIME Sample ID: 2022-12-22-30
TL Number from the TL Form:
Sample Submitted By Organization: Pavement Engineers
Sample Organization Contact: (530) 913-3751
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 12/22/2022
Date that the sample was received by the laboratory/organization performing the testing: 12/23/2022
The quantity of what the sample constitutes: 54
A brief description of the sample: 3728LV
From where was the sample collected: Job Site
Laboratory sample identification: S22-075
Structure unique identifier:
Structure name: Box Culvert
The fabricator/manufacturer/facility name: Shamrock Materials Petaluma
Material Information
The concrete mix design number: 3728LV
The truck number from where the sample was collected: 1465
The batch plant ticket number from where the sample was collected: 431011
Concrete batch plant: Shamrock Petaluma
The fabricator/manufacturer designation for the sample: 3728LV
A detailed description of where the material sample was collected: Back of Truck
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
Test Results
Test 1 of 7
DIME Test ID: 2022-12-22-30-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 12/30/2022
Date Tested: 12/29/2022
Submitted By Organization: Pavement Engineers
Organization Address: 3650 Industrial Boulevard,
Organization City: West Sacramento
Organization State: CA
Organization Zipcode: 95691
Organization Email: michelleh@pavementengineering.com
Organization Phone: (530) 913-3751
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
0 lb
|
Average diameter of cylinder 1
|
3.99 in
|
Average diameter of cylinder 2
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.5 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
6410 psi
|
Maximum load on cylinder 1
|
81775 lb
|
Maximum load on cylinder 2
|
78875 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Correction factor for cylinder 2
|
1.00
|
Age of specimen
|
7 days
|
Age of specimen in hours
|
no data
|
Serial number of delivery ticket, if available
|
431011
|
Test 2 of 7
DIME Test ID: 2022-12-22-30-2
Test Method: ASTM C138-17a: Standard Test Method for Density (Unit Weight), Yield, and Air Content (Gravimetric) of Concrete
Verified Date: 12/30/2022
Date Tested: 12/22/2022
Submitted By Organization: Pavement Engineers
Organization Address: 3650 Industrial Boulevard,
Organization City: West Sacramento
Organization State: CA
Organization Zipcode: 95691
Organization Email: michelleh@pavementengineering.com
Organization Phone: (530) 913-3751
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Identification of concrete represented by the sample
|
3728LV
|
Volume of the measure
|
0.25 ft^3
|
Density of concrete
|
154 lb/ft^3
|
Yield of concrete
|
no data
|
Relative yield of the batch
|
no data
|
Cement content
|
no data
|
Air content
|
no data
|
Test 3 of 7
DIME Test ID: 2022-12-22-30-3
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 12/30/2022
Date Tested: 12/22/2022
Submitted By Organization: Pavement Engineers
Organization Address: 3650 Industrial Boulevard,
Organization City: West Sacramento
Organization State: CA
Organization Zipcode: 95691
Organization Email: michelleh@pavementengineering.com
Organization Phone: (530) 913-3751
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Test 4 of 7
DIME Test ID: 2022-12-22-30-4
Test Method: ASTM C231-17a: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 12/30/2022
Date Tested: 12/22/2022
Submitted By Organization: Pavement Engineers
Organization Address: 3650 Industrial Boulevard,
Organization City: West Sacramento
Organization State: CA
Organization Zipcode: 95691
Organization Email: michelleh@pavementengineering.com
Organization Phone: (530) 913-3751
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Test 5 of 7
DIME Test ID: 2022-12-22-30-5
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 01/05/2023
Date Tested: 01/01/2023
Submitted By Organization: Pavement Engineers
Organization Address: 3650 Industrial Boulevard,
Organization City: West Sacramento
Organization State: CA
Organization Zipcode: 95691
Organization Email: michelleh@pavementengineering.com
Organization Phone: (530) 913-3751
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
0 lb
|
Average diameter of cylinder 1
|
3.99 in
|
Average diameter of cylinder 2
|
3.99 in
|
Average diameter of cylinder 3
|
3.99 in
|
Cross sectional area of cylinder 1
|
12.5 in^2
|
Cross sectional area of cylinder 2
|
12.5 in^2
|
Cross sectional area of cylinder 3
|
12.5 in^2
|
Compressive strength (to nearest 10 psi)
|
7090 psi
|
Maximum load on cylinder 1
|
89665 lb
|
Maximum load on cylinder 2
|
86840 lb
|
Maximum load on cylinder 3
|
89515 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Type of fracture pattern of cylinder 3
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Correction factor for cylinder 2
|
1.00
|
Correction factor for cylinder 3
|
1.00
|
Age of specimen
|
10 days
|
Age of specimen in hours
|
no data
|
Serial number of delivery ticket, if available
|
431011
|
Test 6 of 7
DIME Test ID: 2022-12-22-30-6
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 01/23/2023
Date Tested: 01/01/2023
Submitted By Organization: Pavement Engineers
Organization Address: 3650 Industrial Boulevard,
Organization City: West Sacramento
Organization State: CA
Organization Zipcode: 95691
Organization Email: michelleh@pavementengineering.com
Organization Phone: (530) 913-3751
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
0 lb
|
Average diameter of cylinder 1
|
3.99 in
|
Average diameter of cylinder 2
|
3.99 in
|
Average diameter of cylinder 3
|
3.99 in
|
Cross sectional area of cylinder 1
|
12.5 in^2
|
Cross sectional area of cylinder 2
|
12.5 in^2
|
Cross sectional area of cylinder 3
|
12.5 in^2
|
Compressive strength (to nearest 10 psi)
|
7090 psi
|
Maximum load on cylinder 1
|
89665 lb
|
Maximum load on cylinder 2
|
86840 lb
|
Maximum load on cylinder 3
|
89515 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Type of fracture pattern of cylinder 3
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Correction factor for cylinder 2
|
1.00
|
Correction factor for cylinder 3
|
1.00
|
Age of specimen
|
10 days
|
Age of specimen in hours
|
no data
|
Serial number of delivery ticket, if available
|
431011
|
Test 7 of 7
DIME Test ID: 2022-12-22-30-7
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 03/01/2023
Date Tested: 01/19/2023
Submitted By Organization: Pavement Engineers
Organization Address: 3650 Industrial Boulevard,
Organization City: West Sacramento
Organization State: CA
Organization Zipcode: 95691
Organization Email: michelleh@pavementengineering.com
Organization Phone: (530) 913-3751
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
no data
|
Apparent mass of submerged cylinder 1
|
0 lb
|
Average diameter of cylinder 1
|
4.00 in
|
Average diameter of cylinder 2
|
4.00 in
|
Average diameter of cylinder 3
|
4.00 in
|
Cross sectional area of cylinder 1
|
12.57 in^2
|
Cross sectional area of cylinder 2
|
12.57 in^2
|
Cross sectional area of cylinder 3
|
12.57 in^2
|
Compressive strength (to nearest 10 psi)
|
8510 psi
|
Maximum load on cylinder 1
|
109125 lb
|
Maximum load on cylinder 2
|
104690 lb
|
Maximum load on cylinder 3
|
107170 lb
|
Type of fracture pattern of cylinder 1
|
3
|
Type of fracture pattern of cylinder 2
|
3
|
Type of fracture pattern of cylinder 3
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Correction factor for cylinder 2
|
1.00
|
Correction factor for cylinder 3
|
1.00
|
Age of specimen
|
28 days
|
Age of specimen in hours
|
no data
|
Serial number of delivery ticket, if available
|
431011
|