Project ID: 215150 DEA: 120P0304 EFIS: 1215000024
QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-74-11.5/16.6
Work Description: PLACE HIGH FRICTION SURFACE TREATMENT, HMA & MIDWEST GUARDRAIL SYSTEM.
Location Description: ORANGE COUNTY NEAR SAN JUAN CAPISTRANO FROM 1.0 MILE WEST OF SAN JUAN HOT SPRINGS ROAD TO ORANGE COUNTY LINE
Contractor Name: AMERICAN CIVIL CONSTRUCTORS WEST COAST LLC
Contractor Address: 2990 Bay Vista Court Suit D, Benicia, CA 95122
Resident Engineer: Arsalan Naderi Structure Rep.: Mohammad (Mo) Rousta
DIME Sample ID: 2022-11-17-61
TL Number from the TL Form: Sacramento Caltrans lab
Sample Submitted By Organization: Kwik Bond Polymers
Sample Organization Contact: (760) 518-6064
Type of Sample: Quality Control
Type of Material: High Friction Surface Treatment
Sample Taken Date: 11/17/2022
Date that the sample was received by the laboratory/organization performing the testing: 12/15/2022
The quantity of what the sample constitutes: 2 tankers
A brief description of the sample: 1 gallon can
From where was the sample collected: Source
Laboratory sample identification: 943761
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Kwik Bond Polymers, Benicia
DIME Test ID: 2022-11-17-61-1
Test Method: ASTM D2196-Feb15: Standard Test Methods for Rheological Properties of Non-Newtonian Materials by Rotational Viscometer
Verified Date: 06/29/2023
Date Tested: 01/06/2023
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: Gel time ASTM C881: 24 mins.
Test Result Compliance: complies
Additional Comments When Verified:
DIME Test ID: 2022-11-17-61-2
Test Method: ASTM D638-Dec14: Standard Test Method for Tensile Properties of Plastics
Verified Date: 06/29/2023
Date Tested: 11/28/2022
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: Accepted supplier's results.
Test Result Compliance: complies
Additional Comments When Verified:
Number of specimens tested
|
6
|
Conditioning procedure
|
18/25/50+5/70
|
Speed of testing
|
0.45 in/min
|
Sample 1 Width
|
0.13 in
|
Sample 1 Ultimate strength
|
4277.7 psi
|
Sample 1 Thickness
|
0.493 in
|
Sample 1 Area
|
0.0641 in^2
|
Sample 1 Ultimate Strength Actual
|
274.2 lbs
|
Sample 1 percent elongation
|
66.707 %
|
Sample 1 Time
|
0 MM:SS
|
Sample 2 Width
|
0.133 in
|
Sample 2 Thickness
|
0.492 in
|
Sample 2 Area
|
0.0654 in^2
|
Sample 2 Ultimate strength
|
3636.1 psi
|
Sample 2 Ultimate Strength Actual
|
237.8 lbs
|
Sample 2 percent elongation
|
47.459 %
|
Sample 2 Time
|
0 MM:SS
|
Sample 3 Width
|
0.14 in
|
Sample 3 Thickness
|
0.492 in
|
Sample 3 Area
|
0.0689 in^2
|
Sample 3 Ultimate strength
|
4033.4 psi
|
Sample 3 Ultimate Strength Actual
|
277.9 lbs
|
Sample 3 percent elongation
|
59.065 %
|
Sample 3 Time
|
0 MM:SS
|
Sample 4 Width
|
0.139 in
|
Sample 4 Thickness
|
0.491 in
|
Sample 4 Area
|
0.0682 in^2
|
Sample 4 Ultimate strength
|
4225.8 psi
|
Sample 4 Ultimate Strength Actual
|
288.2 lbs
|
Sample 4 percent elongation
|
62.924 %
|
Sample 4 Time
|
0 MM:SS
|
Sample 5 Width
|
0.147 in
|
Sample 5 Thickness
|
0.488 in
|
Sample 5 Area
|
0.0717 in^2
|
Sample 5 Ultimate strength
|
4149.2 psi
|
Sample 5 Ultimate Strength Actual
|
297.5 lbs
|
Sample 5 percent elongation
|
61.306 %
|
Sample 5 Time
|
0 MM:SS
|
Sample 6 Width
|
0.134 in
|
Sample 6 Thickness
|
0.49 in
|
Sample 6 Area
|
0.0657 in^2
|
Sample 6 Ultimate strength
|
4213.1 psi
|
Sample 6 Ultimate Strength Actual
|
276.8 lbs
|
Sample 6 percent elongation
|
61.18 %
|
Sample 6 Time
|
0 MM:SS
|
Ultimate Strength Average
|
4089 psi
|
Percent Elongation Average
|
60 %
|