Project ID: 214336 DEA: 07302404 EFIS: 0713000488
QA Service Level: 1
DIST-CO-RTE-PM: 07-VEN-101-37/40
Work Description: PADRE JUAN REHAB
Location Description: VEN 101
Contractor Name: GRANITE CONSTRUCTION COMPANY
Contractor Address: 4820 McGrath Street, Suite 101, Ventura, CA 93003
Resident Engineer: Alfred Ira Structure Rep.: Unknown
DIME Sample ID: 2022-10-06-77
TL Number from the TL Form: 22-2652
Sample Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Sample Organization Contact: (213) 817-0387
Type of Sample: Department Acceptance
Type of Material: Concrete
Sample Taken Date: 10/06/2022
Date that the sample was received by the laboratory/organization performing the testing: 10/07/2022
The quantity of what the sample constitutes: 130 CY
A brief description of the sample: 6x12 JPCP cylinders
From where was the sample collected: Manufacturer
Laboratory sample identification: 22-2652
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Granite Construction Ventura
The concrete mix design number: G3-20-PCC-208
The truck number from where the sample was collected: 7
The batch plant ticket number from where the sample was collected: 9024
Concrete batch plant: Granite Construction Ventura
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Loader to wheelborrow
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2022-10-06-77-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 11/17/2022
Date Tested: 11/17/2022
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 817-0387
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Average diameter of cylinder 1
|
6.01 in
|
Average diameter of cylinder 2
|
6.00 in
|
Average diameter of cylinder 3
|
6.01 in
|
Cross sectional area of cylinder 1
|
28.37 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Cross sectional area of cylinder 3
|
28.37 in^2
|
Compressive strength (to nearest 10 psi)
|
4590 psi
|
Maximum load on cylinder 1
|
132136 lb
|
Maximum load on cylinder 2
|
128746 lb
|
Maximum load on cylinder 3
|
129154 lb
|
Compressive strength of cylinder 1
|
4,657.6 psi
|
Type of fracture pattern of cylinder 1
|
2
|
Compressive strength of cylinder 2
|
4,554.2 psi
|
Compressive strength of cylinder 3
|
4,552.5 psi
|
Type of fracture pattern of cylinder 2
|
2
|
Type of fracture pattern of cylinder 3
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1.00
|
Correction factor for cylinder 2
|
1.00
|
Correction factor for cylinder 3
|
1.00
|
Age of specimen
|
42 days
|
Age of specimen in hours
|
no data0 hours
|