Print Report | Back to Sample Detail

Sample Record for 2022-08-08-71

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215784 DEA: 051G2604 EFIS: 0514000131 QA Service Level: 1
DIST-CO-RTE-PM: 05-SCR-17-9.1/9.9
Work Description: CONSTRUCT STRUCTURAL CONCRETE BRIDGE AND ELECTRIFIED BARRIER SYSTEMS.
Location Description: SANTA CRUZ COUNTY NEAR SCOTTS VALLEY FROM 0.6 MILE SOUTH OF LAUREL ROAD TO 0.2 MILE NORTH OF LAUREL ROAD
Contractor Name: GRANITE ROCK COMPANY
Contractor Address: 5225 Hellyer Ave, Suite 220, San Jose, CA 95138
Resident Engineer: Farshad Keshavarzi Structure Rep.: Juan Moreno

Sample Information

DIME Sample ID: 2022-08-08-71
TL Number from the TL Form: Sacramento Caltrans lab
Sample Submitted By Organization: Kwik Bond Polymers
Sample Organization Contact: (760) 518-6064
Type of Sample: Quality Control
Type of Material: High Friction Surface Treatment
Sample Taken Date: 08/08/2022
Date that the sample was received by the laboratory/organization performing the testing: 08/09/2022
The quantity of what the sample constitutes: 9 totes
A brief description of the sample: 1 gallon can
From where was the sample collected: Source
Laboratory sample identification: 943752
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Kwik Bond Polymers, Benicia

Material Information

Mgf. Lot Number(s): 1421669
Batch Number: 1421669
Mix Number: 1421669
Resin Binder Type: Epoxy
Used for Overlay: Yes
Used for Inlay: No

Test Results

Test 1 of 3

DIME Test ID: 2022-08-08-71-1
Test Method: ASTM D2196-Feb15: Standard Test Methods for Rheological Properties of Non-Newtonian Materials by Rotational Viscometer
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 594-1991
This test has been superseded on 03/24/2023.
Reason: retested

Test 2 of 3

DIME Test ID: 2022-08-08-71-2
Test Method: ASTM D638-Dec14: Standard Test Method for Tensile Properties of Plastics
Verified Date: 03/24/2023
Date Tested: 08/15/2022
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: Accepted supplier's results.
Test Result Compliance: complies
Additional Comments When Verified:
Number of specimens tested 5
Conditioning procedure 18/25/50+5/70
Speed of testing 0.45 in/min
Sample 1 Width 0.485 in
Sample 1 Ultimate strength 3749 psi
Sample 1 Thickness 0.169 in
Sample 1 Area 0.082 in^2
Sample 1 Ultimate Strength Actual 307.42 lbs
Sample 1 percent elongation 58.68 %
Sample 1 Time 0 MM:SS
Sample 2 Width 0.483 in
Sample 2 Thickness 0.163 in
Sample 2 Area 0.0787 in^2
Sample 2 Ultimate strength 3659.5 psi
Sample 2 Ultimate Strength Actual 288 lbs
Sample 2 percent elongation 54.92 %
Sample 2 Time 0 MM:SS
Sample 3 Width 0.483 in
Sample 3 Thickness 0.15 in
Sample 3 Area 0.0725 in^2
Sample 3 Ultimate strength 3958.6 psi
Sample 3 Ultimate Strength Actual 287 lbs
Sample 3 percent elongation 62.08 %
Sample 3 Time 0 MM:SS
Sample 4 Width 0.483 in
Sample 4 Thickness 0.157 in
Sample 4 Area 0.0758 in^2
Sample 4 Ultimate strength 4076.5 psi
Sample 4 Ultimate Strength Actual 309 lbs
Sample 4 percent elongation 64.04 %
Sample 4 Time 0 MM:SS
Sample 5 Width 0.491 in
Sample 5 Thickness 0.138 in
Sample 5 Area 0.0678 in^2
Sample 5 Ultimate strength 3997.1 psi
Sample 5 Ultimate Strength Actual 271 lbs
Sample 5 percent elongation 63.14 %
Sample 5 Time 0 MM:SS
Ultimate Strength Average 3888 psi
Percent Elongation Average 61 %

Test 3 of 3

DIME Test ID: 2022-08-08-71-3
Test Method: ASTM D2196-Feb15: Standard Test Methods for Rheological Properties of Non-Newtonian Materials by Rotational Viscometer
Verified Date: 03/24/2023
Date Tested: 11/14/2022
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Viscosity 1876