Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 214670 DEA: 07331004 EFIS: 0716000220
QA Service Level: 1
DIST-CO-RTE-PM: 07-VEN-101-9.0/9.2
Work Description: CONCRETE SLAB REPLACEMENT & GRIND, PAVEMENT & RESURFACE ACE
Location Description: VENTURA COUNTY IN THOUSAND OAKS FROM NORTHBOUND OFF-RAMP TO SOUTHBOUND OFF-RAMP AT CONEJO COMMERCIAL VEHICLE ENFORCEMENT FACILITIES
Contractor Name: POWELL CONSTRUCTORS INC
Contractor Address: 8555 BANANA AVE, FONTANA, CA 92335
Resident Engineer: Ranjit Singh Structure Rep.: Unknown
DIME Sample ID: 2022-10-19-51
TL Number from the TL Form:
Sample Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Sample Organization Contact: (213) 817-0387
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 10/19/2022
Date that the sample was received by the laboratory/organization performing the testing: 10/20/2022
The quantity of what the sample constitutes: 10CY
A brief description of the sample: LCB
From where was the sample collected: Job Site
Laboratory sample identification: 22-2783
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Powell Construction
The concrete mix design number: s30c396L0A
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 589884
Concrete batch plant: National Ready Mix
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Chute discharge into wheel barrel
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2022-10-19-51-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 10/27/2022
Date Tested: 10/26/2022
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 817-0387
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.01 in
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Compressive strength (to nearest 10 psi)
|
540 psi
|
Maximum load on cylinder 1
|
15251 lb
|
Maximum load on cylinder 2
|
15265 lb
|
Compressive strength of cylinder 1
|
539.5 psi
|
Type of fracture pattern of cylinder 1
|
2
|
Compressive strength of cylinder 2
|
538.1 psi
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
7 days
|
Age of specimen in hours
|
0 hours
|