REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Noel AQUINO |
Date Reported: |
08/07/2015 |
|
Address: |
TL Number: |
208308 |
||
City: |
||||
Project Name: REALIGN I-680 TO CONNECT DIRECTLY WITH THE I-80/SR-12 INTERCHANGE. |
||||
Prime Contractor: DESILVA GATES-VIKING JV |
||||
Sample Taken Date: |
06/26/2015 |
Mix Design: |
ct072cr5 |
|
Contractor: Unknown |
Location: IN SOLANO COUNTY NEAR FAIRFIELD. |
|||
Structure unique identifier: Unknown |
||||
Structure name: Unknown |
||||
Location of Pour: Unknown |
The following testing has been tested in accordance with:
ASTM C39-10 : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Specimen | Cross sectional area of cylinder (in^2) | Average diameter of cylinder (in) | Compressive strength of cylinder (psi) | Maximum load on cylinder (lb) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 28.46 | 6.02 | 6440.5 | 183296 | 1 |
2 | 28.37 | 6.01 | 6076.9 | 172401 | 1 |
DIME Test ID: 2015-06-26-3-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 6260
Age of specimen: 42 days
Certified By: Bang Nguyen
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing