Print Report | Back to Sample Detail

Sample Record for 2022-09-07-95

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 993616 DEA: 07357204 EFIS: 0719000061 COOP: 075210 QA Service Level: 2
DIST-CO-RTE-PM: 07-LA-210-20.7/21.7
Work Description: The City of La Canada Flintridge, in partnership with Caltrans, is preparing to construct three sound wall segments, S311, S335, and S336, along the Interstate 210 (I-210).
Location Description: The City of La Canada Flintridge, in partnership with Caltrans, is preparing to construct three sound wall segments, S311, S335, and S336, along the Interstate 210 (I-210).
Contractor Name: PPM Group, Inc.
Contractor Address: 7950 Cherry Avenue, Suite 103,, Fontana, CA 92336
Resident Engineer: Ali Shalviri Structure Rep.: Kwangsuk (KS) Suh

Sample Information

DIME Sample ID: 2022-09-07-95
TL Number from the TL Form:
Sample Submitted By Organization: Sequoia Consultants
Sample Organization Contact: (714) 974-6316
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 09/07/2022
Date that the sample was received by the laboratory/organization performing the testing: 09/08/2022
The quantity of what the sample constitutes: 1 per shift
A brief description of the sample: structural concrete
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: National Ready Mix

Material Information

The concrete mix design number: S75207
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 301952
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: wheelbarrow
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 1

DIME Test ID: 2022-09-07-95-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 10/21/2022
Date Tested: 10/05/2022
Submitted By Organization: Sequoia Consultants
Organization Address: 361 West Grove Avenue,
Organization City: Orange
Organization State: CA
Organization Zipcode: 92865
Organization Email: sranjan@sequoiacon.com
Organization Phone: 1 (714) 974-6316
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.00 in
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.2 in^2
Compressive strength (to nearest 10 psi) 4300 psi
Maximum load on cylinder 1 119590 lb
Maximum load on cylinder 2 124540 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days
Age of specimen in hours 0 hours