Project Information

Project ID: 99999 DEA: 0322222 QA Service Level:
DIST-CO-RTE-PM: 03-SAC,OMG-888,99,80-0.6-0.6
Work Description: THIS PROJECT RECORD WAS ADDED FOR DIME TESTERS - DATA SUBMITTED FOR THIS PROJECT SHOULD NOT BE USED FOR ANY OTHER PURPOSES.
Location Description: THIS PROJECT RECORD WAS ADDED FOR DIME TESTERS - DATA SUBMITTED FOR THIS PROJECT SHOULD NOT BE USED FOR ANY OTHER PURPOSES.
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Michael Maksimovich Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2022-10-21-10
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Materials Management Branch Field Office
Sample Organization Contact: (562) 500-5861
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 10/21/2022
Date that the sample was received by the laboratory/organization performing the testing: 10/21/2022
The quantity of what the sample constitutes: 250cy
A brief description of the sample: structural concrete
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Teichert Matls Vernalis

Material Information

The concrete mix design number: 123456
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 2
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Chute
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 3

DIME Test ID: 2022-10-21-10-1
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Submitted By Organization: CT HQ - Sacramento Materials Management Branch Field Office
Organization Address: 5900 Folsom Boulevard, MS 5,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brett.soldano@dot.ca.gov
Organization Phone: (562) 500-5861
Data has not been verified.

Test 2 of 3

DIME Test ID: 2022-10-21-10-2
Test Method: CTM 504-June 2010: Method of Test for Determining Air Content of Freshly Mixed Concrete by the Pressure Method
Submitted By Organization: CT HQ - Sacramento Materials Management Branch Field Office
Organization Address: 5900 Folsom Boulevard, MS 5,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: brett.soldano@dot.ca.gov
Organization Phone: (562) 500-5861
Data has not been verified.

Test 3 of 3

DIME Test ID: 2022-10-21-10-3
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 12/09/2022
Date Tested: 11/18/2022
Submitted By Organization: ZZCT DIME Development Laboratory A - Bellflower - Internal
Organization Address: 1234 Norwalk Boulevard,
Organization City: Bellflower
Organization State: CA
Organization Zipcode: 90725
Organization Email: test.user@dot.ca.gov
Organization Phone: (213) 555-1212
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 1
Test performed With no density determined
Apparent mass of submerged cylinder 1 0 lb
Average diameter of cylinder 1 6.00 in
Cross sectional area of cylinder 1 28.27 in^2
Compressive strength of cylinder (to nearest 10 psi) 5480 psi
Maximum load on cylinder 1 155000 lb
Type of fracture pattern of cylinder 1 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1.00
Age of specimen 28 days
Age of specimen in hours 0 hours
Serial number of delivery ticket, if available no data