Sample Record for 2022-10-14-24
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 215057 DEA: 010F5304 EFIS: 0116000018
QA Service Level: 1
DIST-CO-RTE-PM: 01-HUM-299,200-R1.8,R2.7
Work Description: RAISE BRIDGE AND HMA PAVING
Location Description: HUMBOLDT COUNTY NEAR ARCATA AT ROUTE 200/299 SEPARATION
Contractor Name: STEELHEAD CONSTRUCTORS INC
Contractor Address: P. O. BOX 997, PALO CEDRO, CA 96073
Resident Engineer: Brian Winter Structure Rep.: Jarred Burrows
Sample Information
DIME Sample ID: 2022-10-14-24
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 10/14/2022
Date that the sample was received by the laboratory/organization performing the testing: 10/17/2022
The quantity of what the sample constitutes: 150 Couplers
A brief description of the sample: Zap Screwlok Type 2 Couplers
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Camblin Steel
Material Information
Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Vinton Steel
Coupler Manufacturer: BarSplice
Intermediate Assembler or Fabricator:
Rebar Size: #8
Coupler Model: Zap Screwlok
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): MM20104043
Rebar Heat Number(s): 2211937
Rebar Size 2 :
Coupler Unique ID: SL-17-03
Test Results
Test 1 of 3
DIME Test ID: 2022-10-14-24-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 10/20/2022
Date Tested: 10/18/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: service splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 1 | | No. 8/25mm | 2 | 0.0011 | 0.79 | 76723 | 97118 | service splice | spaine |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
Small
|
Test 2 of 3
DIME Test ID: 2022-10-14-24-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 10/20/2022
Date Tested: 10/18/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: service splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 2 | | No. 8/25mm | 2 | 0 | 0.79 | 75311 | 95330 | service splice | spaine |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
|
Test 3 of 3
DIME Test ID: 2022-10-14-24-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 10/20/2022
Date Tested: 10/18/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: service splice
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 3 | | No. 8/25mm | 2 | 0 | 0.79 | 76700 | 97088 | service splice | spaine |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
|