REPORT OF LABORATORY TESTING

Resident Engineer:

Fabio La Serna

Date Reported:

11/04/2022

Address:

TL Number:

City:

Project Name: CIP BRIDGES, CONSTRUCT ROADWAY, RETAINING WALLS AND MODIFY ELECTRICAL.

Prime Contractor: GHILOTTI CONSTRUCTION CO. INC. (RILEY GENAZZI & JOSH SERAFINO)

Sample Taken Date:

09/23/2022

Mix Design:

3728LV

Contractor: Unknown

Location: MARIN COUNTY IN AND NEAR NOVATO FROM 0.1 MILE SOUTH OF FRANKLIN AVENUE OVERHEAD TO 0.5 MILE SOUTH OF SAN ANTONIO CREEK BRIDGE

Structure unique identifier: 21-0092L 21-0090L

Structure name: Olive Ave UC Franklin Ave OH

Location of Pour: TRIAL BATCH


The following testing has been tested in accordance with:

ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens

Capped in accordance with ASTM C617/CTM521

SpecimenAverage diameter of cylinder (in)Cross sectional area of cylinder (in^2)Maximum load on cylinder (lb)Compressive strength of cylinder (psi)Type of fracture pattern of cylinder
14.0212.69780336148.01
24.0212.69728375739.01
34.0212.697201956741

DIME Test ID: 2022-09-23-37-1
Number of specimens: 3
Compressive strength (to nearest 10 psi): 5850
Age of specimen: 7 days
Certified By: Spencer Adams


ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens

Capped in accordance with ASTM C617/CTM521

SpecimenAverage diameter of cylinder (in)Cross sectional area of cylinder (in^2)Maximum load on cylinder (lb)Compressive strength of cylinder (psi)Type of fracture pattern of cylinder
14.0212.69722475692.04
24.0212.69761405999.04
34.0112.638100764144

DIME Test ID: 2022-09-23-37-2
Number of specimens: 3
Compressive strength (to nearest 10 psi): 6040
Age of specimen: 14 days
Certified By: Ryan Crawford


ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens

Capped in accordance with ASTM C617/CTM521

SpecimenAverage diameter of cylinder (in)Cross sectional area of cylinder (in^2)Maximum load on cylinder (lb)Compressive strength of cylinder (psi)Type of fracture pattern of cylinder
14.0212.69813056406.01
24.0312.76882406918.01
34.0312.768878969611

DIME Test ID: 2022-09-23-37-3
Number of specimens: 3
Compressive strength (to nearest 10 psi): 6760
Age of specimen: 21 days
Certified By: Spencer Adams


ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens

Capped in accordance with ASTM C617/CTM521

SpecimenAverage diameter of cylinder (in)Cross sectional area of cylinder (in^2)Maximum load on cylinder (lb)Compressive strength of cylinder (psi)Type of fracture pattern of cylinder
14.0212.69915247211.02
24.0212.69792786246.01
34.0212.698284765271

DIME Test ID: 2022-09-23-37-4
Number of specimens: 3
Compressive strength (to nearest 10 psi): 6660
Age of specimen: 28 days
Certified By: Spencer Adams


ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens

Capped in accordance with ASTM C617/CTM521

SpecimenAverage diameter of cylinder (in)Cross sectional area of cylinder (in^2)Maximum load on cylinder (lb)Compressive strength of cylinder (psi)Type of fracture pattern of cylinder
14.0212.69892477032.01
24.0212.69707565575.01
34.0212.696584951882

DIME Test ID: 2022-09-23-37-5
Number of specimens: 3
Compressive strength (to nearest 10 psi): 5930
Age of specimen: 42 days
Certified By: Spencer Adams



Summary of Items Observed and Conversations:

Comments: This report is for the purpose of reporting test results.
Should you require recommendations concerning repairs or remedial efforts please contact the METS representative,
who represents the Materials Engineering and Testing Services for your project.

*Subject to final inspection by the Resident Engineer.




TL- Report of Laboratory Testing