Gavin Newsom, Governor |
DEPARTMENT OF TRANSPORTATIONDIVISION OF ENGINEERING SERVICES MATERIALS ENGINEERING AND TESTING SERVICES Concrete Materials Testing Branch 5900 Folsom Blvd. Sacramento, CA 95819 916-227-7205 |
Contract # 042J7204 Cty CC Rte 580 PM 1.17 Vendor # |
REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Luis Melendez |
Date Reported: |
10/20/2022 |
|
Address: |
TL Number: |
003 |
||
City: |
||||
Project Name: STEGE DRAIN SUPER-STRUCTURE, PRECAST VOIDED SLABS |
||||
Prime Contractor: GORDON N BALL INC |
||||
Sample Taken Date: |
09/22/2022 |
Mix Design: |
4EACC5KS |
|
Contractor: Unknown |
Location: CONTRA COSTA COUNTY IN RICHMOND FROM 0.3 MILE EAST OF STEGE DRAIN BRIDGE TO 0.3 MILE WEST OF BAYVIEW AVENUE OVERCROSSING |
|||
Structure unique identifier: |
||||
Structure name: |
||||
Location of Pour: |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 5.98 | 28.09 | 167431 | 5961.0 | 1 |
2 | 5.98 | 28.09 | 156954 | 5588.0 | 1 |
DIME Test ID: 2022-09-22-37-1
Number of specimens: 2
Compressive strength (to nearest 10 psi): 5770
Age of specimen: 28 days
Certified By: Spencer Adams
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing