Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 212720 DEA: 07291404 EFIS: 0712000094
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-1-55-58
Work Description: TRANCAS CREEK BRIDGE REPLACEMENT
Location Description: IN LOS ANGELES IN CITY OF MALIBU AT TRANCAS CREEK BRIDGE (53-0027).
Contractor Name: STACY AND WITBECK, INC.
Contractor Address: 3939 Atlantic Ave Suite 114, Long Beach, CA 90807
Resident Engineer: Dan Leon Structure Rep.: Frank Lofti
DIME Sample ID: 2022-08-31-49
TL Number from the TL Form:
Sample Submitted By Organization: Bethlehem Construction, Incorporated
Sample Organization Contact: (661) 758-1001
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 08/31/2022
Date that the sample was received by the laboratory/organization performing the testing: 08/31/2022
The quantity of what the sample constitutes: 24CY
A brief description of the sample: Voided Slab
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Bethlehem Construction
The concrete mix design number: SCC-ASH-32_3
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 0009927
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: MIDDLE OF THE LOAD
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2022-08-31-49-1
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 09/20/2022
Date Tested: 09/07/2022
Submitted By Organization: Bethlehem Construction, Incorporated
Organization Address: 425 J Street,
Organization City: Wasco
Organization State: CA
Organization Zipcode: 93280
Organization Email: keithl@bethlehemconstruction.com
Organization Phone: (661) 758-1001
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
3
|
Test performed
|
With no density determined
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Capped in accordance with?
|
ASTM C1231 - Unbonded Elastomeric Pad Cap
|
Average diameter of cylinder 3
|
6.00 in
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Cross sectional area of cylinder 3
|
28.27 in^2
|
Compressive strength (to nearest 10 psi)
|
7330 psi
|
Maximum load on cylinder 1
|
199820 lb
|
Maximum load on cylinder 2
|
191930 lb
|
Maximum load on cylinder 3
|
192160 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Type of fracture pattern of cylinder 3
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Correction factor for cylinder 3
|
1
|
Age of specimen
|
7 days
|
Age of specimen in hours
|
no data0 hours
|