DEPARTMENT OF TRANSPORTATIONDIVISION OF ENGINEERING SERVICES MATERIALS ENGINEERING AND TESTING SERVICES Concrete Materials Testing Branch 5900 Folsom Blvd. Sacramento, CA 95819 916-227-7205 |
Contract # 041W0004 Cty MRN Rte 1 PM 1.0 Vendor # |
REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Isaac Mai |
Date Reported: |
09/20/2022 |
|
Address: |
TL Number: |
280874 |
||
City: |
||||
Project Name: INSTALL RECTANGULAR RAPID FLASHING BEACON (RRFB) AND S |
||||
Prime Contractor: Gremelli Industries |
||||
Sample Taken Date: |
09/06/2022 |
Mix Design: |
01-6 |
|
Contractor: Unknown |
Location: |
|||
Structure unique identifier: |
||||
Structure name: |
||||
Location of Pour: |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 4.02 | 12.69 | 46207 | 3641.0 | 4 |
2 | 4.02 | 12.69 | 65457 | 5157.0 | 4 |
3 | 4.02 | 12.69 | 36609 | 2884 | 4 |
DIME Test ID: 2022-09-06-21-1
Number of specimens: 3
Compressive strength (to nearest 10 psi): 3890
Age of specimen: 14 days
Certified By: Spencer Adams
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing