Project Information

Project ID: 213707 DEA: 081C38U4 EFIS: 0817000196 QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-10-6.7/R25.1
Work Description: Remove concrete pavement and base, and place HMA and JPCP
Location Description: ROUTE 10/60 SEPARATION IN BEAUMONT TO ROUTE 10/111 SEPARATION NEAR CABAZON.
Contractor Name: Coffman Specialties
Contractor Address: 9685 Via Excelencia, San Diego, CA 92126
Resident Engineer: Elvira Lenart Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2022-08-29-25
TL Number from the TL Form: 73RR
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 08/29/2022
Date that the sample was received by the laboratory/organization performing the testing: 08/30/2022
The quantity of what the sample constitutes: 6
A brief description of the sample: concrete cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 1012-73RR
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Coffman Specialties, Inc

Material Information

The concrete mix design number: 1906-17
The truck number from where the sample was collected: 62
The batch plant ticket number from where the sample was collected: 8
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: I 10 Station 429.75 Main St On Ramp Loop
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 1

DIME Test ID: 2022-08-29-25-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 09/07/2022
Date Tested: 09/05/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.18 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 4140 psi
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 5.99 in
Compressive strength of cylinder 1 4143.9 psi
Compressive strength of cylinder 2 4131.1 psi
Maximum load on cylinder 1 116775 lb
Maximum load on cylinder 2 116415 lb
Type of fracture pattern of cylinder 1 2
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days