Project ID: 993302 DEA: 081J2104 EFIS: 0817000240
QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-60-R1.4
Work Description: PLACE LCB RAPID SETTING AND JOINTED PLAIN CONCRETE PAVEMENT.
Location Description: SAN BERNARDINO COUNTY IN CHINO AT RAMONA AVENUE OVERCROSSING
Contractor Name: RV CONCRETE INC
Contractor Address: 605 E. COMMERCIAL ST., ANAHEIM CA 92801
Resident Engineer: Xavier Avila Structure Rep.: Unknown
DIME Sample ID: 2022-08-06-7
TL Number from the TL Form: 1043-1
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 08/06/2022
Date that the sample was received by the laboratory/organization performing the testing: 08/11/2022
The quantity of what the sample constitutes: 2
A brief description of the sample: Concrete Cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 1043-1
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Short Load Concrete
The concrete mix design number: CTS-30-RAM
The truck number from where the sample was collected: NA
The batch plant ticket number from where the sample was collected: NA
Concrete batch plant:
The fabricator/manufacturer designation for the sample: NA
A detailed description of where the material sample was collected: EB60 Ramona STA 6900
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2022-08-06-7-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 08/15/2022
Date Tested: 08/15/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.37 in^2
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Compressive strength (to nearest 10 psi)
|
950 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.01 in
|
Compressive strength of cylinder 1
|
961.1 psi
|
Compressive strength of cylinder 2
|
947.8 psi
|
Maximum load on cylinder 1
|
27170 lb
|
Maximum load on cylinder 2
|
26890 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
2
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
9 days
|