Project ID: 215221 DEA: 07332604 EFIS: 0716000287
QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-10-R12.4/14.9
Work Description: REMOVE RAISED ISLAND, CONSTRUCT CONCRETE BARRIER AND INSTALL LIGHTING.
Location Description: THE COUNTY AND CITY OF LOS ANGELES FROM 0.1 MILE EAST OF ARLINGTON AVENUE OVERCROSSING TO 0.7 MILE EAST OF ROUTE 10/110 SEPARATION
Contractor Name: CHUMO CONSTRUCTION INC
Contractor Address: 14425 Joanbridge St, Baldwin Park, CA 91706
Resident Engineer: Gilbert Trujillo Structure Rep.: Bernabe Contreras
DIME Sample ID: 2022-07-06-45
TL Number from the TL Form:
Sample Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Sample Organization Contact: (213) 817-0387
Type of Sample: Acceptance
Type of Material: Concrete
Sample Taken Date: 07/06/2022
Date that the sample was received by the laboratory/organization performing the testing: 07/07/2022
The quantity of what the sample constitutes: 250 yd3
A brief description of the sample: 6x12 LCB cylinders
From where was the sample collected: Job Site
Laboratory sample identification: 22-1652
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Robertson's
The concrete mix design number: SC270N31
The truck number from where the sample was collected: 4
The batch plant ticket number from where the sample was collected: 6824391
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Discharge from concrete truck into wheelbarrow.
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:
DIME Test ID: 2022-07-06-45-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 07/13/2022
Date Tested: 07/13/2022
Submitted By Organization: CT D07 - Materials Field Laboratory, Unit 1953
Organization Address: 1940 South Workman Mill Road,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90601
Organization Email: chad.chotibhongs@dot.ca.gov
Organization Phone: (213) 817-0387
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used?
|
US Units
|
Number of specimens
|
2
|
Test performed
|
With no density determined
|
Cross sectional area of cylinder 1
|
28.27 in^2
|
Cross sectional area of cylinder 2
|
28.27 in^2
|
Capped in accordance with?
|
ASTM C617 - Sulfur Mortar Cap
|
Compressive strength (to nearest 10 psi)
|
710 psi
|
Average diameter of cylinder 1
|
6.00 in
|
Average diameter of cylinder 2
|
6.00 in
|
Compressive strength of cylinder 1
|
699.5 psi
|
Compressive strength of cylinder 2
|
711.0 psi
|
Maximum load on cylinder 1
|
19775 lb
|
Maximum load on cylinder 2
|
20101 lb
|
Type of fracture pattern of cylinder 1
|
2
|
Type of fracture pattern of cylinder 2
|
3
|
Comment on any defect in either specimen or caps (Max 250 Characters)
|
no data
|
Correction factor for cylinder 1
|
1
|
Correction factor for cylinder 2
|
1
|
Age of specimen
|
6 days
|