Print Report | Back to Sample Detail

Sample Record for 2021-11-05-37

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 209820 DEA: 04297634 EFIS: 0415000040 COOP: 042548 QA Service Level: 1
DIST-CO-RTE-PM: 04-ALA-84,680-17.9/21
Work Description: ROUTE 84 WIDENING (4-LANE EXPRESSWAY) FROM I-680 TO PIGEON PASS, INCLUDING INTERSECTION, DRAINAGE IMPROVEMENTS AND UTILITY RELOCATION.
Location Description: ALAMEDA COUNTY IN AND NEAR SUNOL, PLEASANTON, AND LIVERMORE ON ROUTE 84 FROM 0.1 MILE EAST OF ROUTE 680 TO 0.1 MILE SOUTH OF RUBY HILL DRIVE AND ON ROUTE 680 FROM 1.2 MILES SOUTH TO 1.8 MILES NORTH OF ROUTE 84
Contractor Name: Bay Cities Paving & Grading
Contractor Address: 1450 Civic Ct. BLDG B #400, Concord CA, 94520
Resident Engineer: Paramjit Pandher Structure Rep.: Ehab Wahed

Sample Information

DIME Sample ID: 2021-11-05-37
TL Number from the TL Form:
Sample Submitted By Organization: Rinker Materials
Sample Organization Contact: (916) 381-3910
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 11/05/2021
Date that the sample was received by the laboratory/organization performing the testing: 11/05/2021
The quantity of what the sample constitutes: days production
A brief description of the sample: 4x8 concrete cylinders
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Forterra

Material Information

The concrete mix design number: mix 5
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 2
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Besser Hopper
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 2

DIME Test ID: 2021-11-05-37-1
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/25/2022
Date Tested: 11/12/2021
Submitted By Organization: Rinker Materials
Organization Address: 7020 Tokay Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95828
Organization Email: Edgar.Benitez@Rinkerpipe.com
Organization Phone: (209) 401-6972
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Compressive strength (to nearest 10 psi) 5360 psi
Maximum load on cylinder 1 66225 lb
Maximum load on cylinder 2 68540 lb
Type of fracture pattern of cylinder 1 5
Type of fracture pattern of cylinder 2 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days
Age of specimen in hours no data

Test 2 of 2

DIME Test ID: 2021-11-05-37-2
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 06/25/2022
Date Tested: 12/03/2021
Submitted By Organization: Rinker Materials
Organization Address: 7020 Tokay Avenue,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95828
Organization Email: Edgar.Benitez@Rinkerpipe.com
Organization Phone: (209) 401-6972
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 4.00 in
Average diameter of cylinder 2 4.00 in
Cross sectional area of cylinder 1 12.57 in^2
Cross sectional area of cylinder 2 12.57 in^2
Compressive strength (to nearest 10 psi) 6320 psi
Maximum load on cylinder 1 78965 lb
Maximum load on cylinder 2 79995 lb
Type of fracture pattern of cylinder 1 5
Type of fracture pattern of cylinder 2 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days
Age of specimen in hours no data