Print Report | Back to Sample Detail

Sample Record for 2022-05-10-37

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 214663 DEA: 081F7304 EFIS: 0815000034 QA Service Level: 1
DIST-CO-RTE-PM: 08-SBD-215-2.7
Work Description: REPLACE CONCRETE BRIDGE, PLACE CONCRETE PCPS GIRDERS AND HMA.
Location Description: SAN BERNARDINO COUNTY IN COLTON AT WASHINGTON STREET OVERCROSSING
Contractor Name: SECURITY PAVING COMPANY, INC.
Contractor Address: 13170 TELFAIR AVE, SYLMAR, CA, 91342
Resident Engineer: Shaine Shahidi Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2022-05-10-37
TL Number from the TL Form: 1
Sample Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Sample Organization Contact: 213-792-4794
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 05/10/2022
Date that the sample was received by the laboratory/organization performing the testing: 05/11/2022
The quantity of what the sample constitutes: 4
A brief description of the sample: 6x12
From where was the sample collected: Job Site
Laboratory sample identification: 1037-512
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: NA

Material Information

The concrete mix design number: 1611614
The truck number from where the sample was collected: 10067790
The batch plant ticket number from where the sample was collected: 52770088
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: NB 215 Washington Exit RW 105 load 3
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 2

DIME Test ID: 2022-05-10-37-1
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 06/06/2022
Date Tested: 05/24/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 28.09 in^2
Cross sectional area of cylinder 2 28.18 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 4880 psi
Average diameter of cylinder 1 5.98 in
Average diameter of cylinder 2 5.99 in
Compressive strength of cylinder 1 4912.8 psi
Compressive strength of cylinder 2 4839.2 psi
Maximum load on cylinder 1 138000 lb
Maximum load on cylinder 2 136370 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 14 days

Test 2 of 2

DIME Test ID: 2022-05-10-37-2
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617 - Sulfur Mortar Cap
Verified Date: 06/10/2022
Date Tested: 06/07/2022
Submitted By Organization: CT D08 - Fontana Southern Regional Laboratory
Organization Address: 13970 Victoria Street,
Organization City: Fontana
Organization State: CA
Organization Zipcode: 92336
Organization Email: jose.guzman@dot.ca.gov
Organization Phone: 9098293029
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Cross sectional area of cylinder 1 27.99 in^2
Cross sectional area of cylinder 2 27.99 in^2
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Compressive strength (to nearest 10 psi) 5520 psi
Average diameter of cylinder 1 5.97 in
Average diameter of cylinder 2 5.97 in
Compressive strength of cylinder 1 5501.3 psi
Compressive strength of cylinder 2 5533.6 psi
Maximum load on cylinder 1 153980 lb
Maximum load on cylinder 2 154885 lb
Type of fracture pattern of cylinder 1 1
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days