Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 993445 DEA: 101M3504 EFIS: 1020000181
QA Service Level: 1
DIST-CO-RTE-PM: 10-SJ-132-L0.7/5.8
Work Description: REPLACE APPROACH SLAB AND PLACE POLYESTER CONCRETE OVERLAY.
Location Description: SAN JOAQUIN COUNTY NEAR VERNALIS AT VARIOUS LOCATIONS FROM ROUTE 132 EAST/580 SEPARATION TO ROUTE 132/33 SEPARATION AND OVERHEAD
Contractor Name: Truesdell Corporation
Contractor Address: 1310 W. 23rd Street, Tempe, AZ 85282
Resident Engineer: David Abledu Structure Rep.: Kyle Sanford
DIME Sample ID: 2022-04-12-29
TL Number from the TL Form: 943107
Sample Submitted By Organization: Kwik Bond Polymers
Sample Organization Contact: (760) 518-6064
Type of Sample: Quality Control
Type of Material: Polyester
Sample Taken Date: 04/12/2022
Date that the sample was received by the laboratory/organization performing the testing: 04/13/2022
The quantity of what the sample constitutes: 11 Tankers
A brief description of the sample: 1 gallon can
From where was the sample collected: Source
Laboratory sample identification: 943107
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Kwik Bond Polymers and Polynt
DIME Test ID: 2022-04-12-29-1
Test Method: ASTM D2196-Feb15: Standard Test Methods for Rheological Properties of Non-Newtonian Materials by Rotational Viscometer
Verified Date: 05/13/2022
Date Tested: 05/09/2022
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
DIME Test ID: 2022-04-12-29-2
Test Method: ASTM D1475-Nov13: Standard Test Method For Density of Liquid Coatings, Inks, and Related Products
Verified Date: 05/13/2022
Date Tested: 05/09/2022
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Density Units
|
pounds/gallons
|
Liquid Density (pounds per gallon)
|
8.91
|
DIME Test ID: 2022-04-12-29-3
Test Method: ASTM D638-Dec14: Standard Test Method for Tensile Properties of Plastics
Verified Date: 05/13/2022
Date Tested: 05/10/2022
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Number of specimens tested
|
6
|
Conditioning procedure
|
18/25/50+5/70
|
Speed of testing
|
0.45 in/min
|
Sample 1 Width
|
0.491 in
|
Sample 1 Ultimate strength
|
3140.4 psi
|
Sample 1 Thickness
|
0.264 in
|
Sample 1 Area
|
0.1296 in^2
|
Sample 1 Ultimate Strength Actual
|
407 lbs
|
Sample 1 percent elongation
|
28 %
|
Sample 1 Time
|
1 MM:SS
|
Sample 2 Width
|
0.49 in
|
Sample 2 Thickness
|
0.252 in
|
Sample 2 Area
|
0.1235 in^2
|
Sample 2 Ultimate strength
|
3368.4 psi
|
Sample 2 Ultimate Strength Actual
|
416 lbs
|
Sample 2 percent elongation
|
30 %
|
Sample 2 Time
|
2 MM:SS
|
Sample 3 Width
|
0.489 in
|
Sample 3 Thickness
|
0.243 in
|
Sample 3 Area
|
0.1188 in^2
|
Sample 3 Ultimate strength
|
3518.5 psi
|
Sample 3 Ultimate Strength Actual
|
418 lbs
|
Sample 3 percent elongation
|
41 %
|
Sample 3 Time
|
2 MM:SS
|
Sample 4 Width
|
0.49 in
|
Sample 4 Thickness
|
0.264 in
|
Sample 4 Area
|
0.1294 in^2
|
Sample 4 Ultimate strength
|
3330.8 psi
|
Sample 4 Ultimate Strength Actual
|
431 lbs
|
Sample 4 percent elongation
|
48 %
|
Sample 4 Time
|
2 MM:SS
|
Sample 5 Width
|
0.49 in
|
Sample 5 Thickness
|
0.265 in
|
Sample 5 Area
|
0.1299 in^2
|
Sample 5 Ultimate strength
|
3487.3 psi
|
Sample 5 Ultimate Strength Actual
|
453 lbs
|
Sample 5 percent elongation
|
24 %
|
Sample 5 Time
|
1 MM:SS
|
Sample 6 Width
|
0.487 in
|
Sample 6 Thickness
|
0.262 in
|
Sample 6 Area
|
0.1276 in^2
|
Sample 6 Ultimate strength
|
3393.4 psi
|
Sample 6 Ultimate Strength Actual
|
433 lbs
|
Sample 6 percent elongation
|
38 %
|
Sample 6 Time
|
0 MM:SS
|
Ultimate Strength Average
|
3373 psi
|
Percent Elongation Average
|
35 %
|
DIME Test ID: 2022-04-12-29-4
Test Method: ASTM D2369-Jul10: Standard Test Method for Volatile Content of Coatings
Verified Date: 05/13/2022
Date Tested: 05/09/2022
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Mean of two volatile content determination
|
45
|
DIME Test ID: 2022-04-12-29-5
Test Method: CTM 551-August 2012: Method of Test for Determining Suitability of Materials for Overlayment and Repair of Portland Cement Concrete Pavements and Structures
Verified Date: 05/13/2022
Date Tested: 05/10/2022
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test: Only two beams fabricated. Average psi is 522.
Test Result Compliance: complies
Additional Comments When Verified:
Curing history for Sample 1
|
24hr
|
Maximum applied load (P) for Sample 1
|
983 lb
|
Span length for Sample 1
|
9 in
|
Break location for Sample 1
|
bond
|
Specimen defects/notes for Sample 1
|
no data
|
Surface type for Sample 1
|
SSD
|
Modulus of rupture (R) for Sample 1
|
491.5 psi
|
Curing history for Sample 2
|
24hr
|
Maximum applied load (P) for Sample 2
|
1104 lb
|
Span length for Sample 2
|
9 in
|
Break location for Sample 2
|
bond
|
Specimen defects/notes for Sample 2
|
no data
|
Surface type for Sample 2
|
SSD
|
Modulus of rupture (R) for Sample 2
|
552 psi
|
Curing history for Sample 3
|
24hr
|
Maximum applied load (P) for Sample 3
|
0 lb
|
Span length for Sample 3
|
9 in
|
Break location for Sample 3
|
bond
|
Specimen defects/notes for Sample 3
|
no data
|
Surface type for Sample 3
|
SSD
|
Modulus of rupture (R) for Sample 3
|
0 psi
|
DIME Test ID: 2022-04-12-29-6
Test Method: SCAQMD 309-91-Feb93: Determination of Static Volatile Emissions
Verified Date: 05/13/2022
Date Tested: 05/11/2022
Submitted By Organization: CT HQ - Sacramento Concrete Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: spencer.adams@dot.ca.gov
Organization Phone: (916) 227-5716
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Diameter of lid
|
154.18 mm
|
Room Temperature
|
70.6 f
|
Tare weight
|
no data
|
Initial weight
|
100.02 grams
|
Weight at 5 minutes
|
99.92 grams
|
Weight at 10 minutes
|
99.85 grams
|
Weight at 15 minutes
|
99.78 grams
|
Weight at 20 minutes
|
99.7 grams
|
Weight at 25 minutes
|
99.62 grams
|
Weight at 30 minutes
|
99.55 grams
|
Final weight
|
99.55 grams
|
Total weight loss
|
0.47 grams
|
Calculated radius of gallon can lid in cm
|
7.709 cm
|
Lid Factor
|
53.562 m^2
|
Volatile emission
|
25.174 grams/m^2
|