Project ID: 8801 DEA: AML-CEM EFIS: AML-CEM
QA Service Level:
DIST-CO-RTE-PM: 59---
Work Description: Special project for Cementitious Materials for use in Concrete Authorized Material List (AML)
Location Description:
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Unknown Structure Rep.: Unknown
DIME Sample ID: 2022-03-21-55
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Sample Organization Contact: (916) 227-7071
Type of Sample: Annual Source Testing
Type of Material: Cementitious
Sample Taken Date: 03/21/2022
Date that the sample was received by the laboratory/organization performing the testing: 03/21/2022
The quantity of what the sample constitutes: 1 Bucket
A brief description of the sample: Natural Pozzolan
From where was the sample collected: Source
Laboratory sample identification: CM225203
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Global Pozzolan
DIME Test ID: 2022-03-21-55-2
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 07/06/2022
Date Tested: 05/10/2022
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test: 7 day test
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
yes
|
Age of specimen
|
7 days
|
The amount of flow
|
110 %
|
The amount of water used
|
50.4 %
|
Compressive strength of 1st specimen
|
0 psi
|
Compressive strength of 2nd specimen
|
0 psi
|
Compressive strength of 3rd specimen
|
0 psi
|
Average Compressive strength (to nearest 10 psi)
|
3960 psi
|
Average Compressive strength (to nearest 10 psi) control group
|
5160 psi
|
Strength Activity Index of Portland Cement per ASTM C109
|
77 %
|
DIME Test ID: 2022-03-21-55-3
Test Method: ASTM C109-16a: Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50-mm] Cube Specimens)
Verified Date: 07/06/2022
Date Tested: 05/31/2022
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Will control cubes be used per ASTM C311?
|
yes
|
Age of specimen
|
28 days
|
The amount of flow
|
110 %
|
The amount of water used
|
50.4 %
|
Compressive strength of 1st specimen
|
5103 psi
|
Compressive strength of 2nd specimen
|
5008 psi
|
Compressive strength of 3rd specimen
|
5071 psi
|
Average Compressive strength (to nearest 10 psi)
|
5060 psi
|
Average Compressive strength (to nearest 10 psi) control group
|
6090 psi
|
Strength Activity Index of Portland Cement per ASTM C109
|
83 %
|
DIME Test ID: 2022-03-21-55-4
Test Method: ASTM C430-8: Standard Test Method for Fineness of Hydraulic Cement by the 45-μm (No. 325) Sieve
Verified Date: 07/06/2022
Date Tested: 04/28/2022
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Correction Factor (CF)
|
.32
|
Corrected Residue (Rc)
|
5.5
|
DIME Test ID: 2022-03-21-55-5
Test Method: ASTM C1567-13: Standard Test Method for Determining the Potential Alkali-Silica Reactivity of Combinations of Cementitious Materials and Aggregate (Accelerated Mortar-Bar Method)
Verified Date: 07/06/2022
Date Tested: 06/20/2022
Submitted By Organization: CT HQ - Sacramento Cement Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: ben.lenz@dot.ca.gov
Organization Phone: (916) 227-7071
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Type and source of Portland cement
|
Nevada Fernley Type II
|
Alkali content of cement as percent potassium oxide
|
na
|
Alkali content of cement as percent sodium oxide
|
na
|
Alkali content of cement as percent calculated sodium oxide
|
.61
|
Comments about aggregate preparation
|
no data
|
Comments about specimen features
|
no data
|
Amount of mixing water
|
207 ml
|
Percent change in length specimen 1 (zero reading)
|
0.0290 %
|
Percent change in length specimen 2 (zero reading)
|
0.0250 %
|
Percent change in length specimen 3 (zero reading)
|
0.0280 %
|
Percent change in length specimen 1 (first reading)
|
7.2050 %
|
Percent change in length specimen 2 (first reading)
|
7.1570 %
|
Percent change in length specimen 3 (first reading)
|
7.2940 %
|
Percent change in length specimen 1 (second reading)
|
7.2050 %
|
Percent change in length specimen 2 (second reading)
|
7.1570 %
|
Percent change in length specimen 3 (second reading)
|
7.2940 %
|
Percent change in length specimen 1 (third reading)
|
0.0120 %
|
Percent change in length specimen 2 (third reading)
|
0.0130 %
|
Percent change in length specimen 3 (third reading)
|
0.0130 %
|
Average percent change in length (zero reading)
|
0.0273 %
|
Average percent change in length (first reading)
|
7.2187 %
|
Average percent change in length (second reading)
|
7.2187 %
|
Average percent change in length (third reading)
|
0.0127 %
|