Project Information

Project ID: 215063 DEA: 032F5704 EFIS: 0300020615 QA Service Level: 1
DIST-CO-RTE-PM: 03-PLA-80-46.3/63.5
Work Description: Replace 4 Bridges (OC) on Highway 80 from Crystal Springs to Cisco Grove (Baxter, Drum Forebay)
Location Description:
Contractor Name: Walsh Construction Company II, LLC (Walsh)
Contractor Address: 1390 Willow Pass Road Suite 950, Concord, CA 94520
Resident Engineer: Tad Sampson Structure Rep.: Jimmer Ross

Sample Information

DIME Sample ID: 2022-04-22-1
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Headed Bars
Sample Taken Date: 04/22/2022
Date that the sample was received by the laboratory/organization performing the testing: 04/25/2022
The quantity of what the sample constitutes: 24
A brief description of the sample: ASTM A706 GR60 HRC 120 T-Heads
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: HRC- Fountain Valley

Material Information

Production or Authorization Testing: Production Testing
Rebar Heat Number(s): 2111700
Head Manufacturer Lot Number(s): 1
Rebar Size: #10
Headed Bar Model Name: HRC 120 T Heads
Size of Head: Full Size - 9x
Head Connection Type: Friction Weld
Head Shape: Square
Rebar Manufacturer: Vinton Steel
Head Manufacturer: Niagra LaSalle Corp
Head Fabricator: HRC Fountain Valley
Material Standard Code: ASTM A706
Headed Bar Unique ID:

Test Results

Test 1 of 3

DIME Test ID: 2022-04-22-1-1
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/27/2022
Date Tested: 04/26/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: ok necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
11.2711305489019ok neckingspaine
Temperature 72 f
UTM 400kip

Test 2 of 3

DIME Test ID: 2022-04-22-1-2
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/27/2022
Date Tested: 04/26/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: ok necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
11.2711600991346ok neckingspaine
Temperature 72 f
UTM 400kip

Test 3 of 3

DIME Test ID: 2022-04-22-1-3
Test Method: ASTM A970-18: Standard Specification for Headed Steel Bars for Concrete Reinforcement (Tensile)
Verified Date: 04/27/2022
Date Tested: 04/26/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: ok necking
Test Result Compliance:
Additional Comments When Verified:
Number of Headed Bar Samples 1
Lot #Area (sqin)Peak Load (lbf)Tensile Strength (psi)CommentsTested By
11.2711895793667ok neckingspaine
Temperature 72 f
UTM 400kip