Gavin Newsom, Governor |
DEPARTMENT OF TRANSPORTATIONDIVISION OF ENGINEERING SERVICES MATERIALS ENGINEERING AND TESTING SERVICES Concrete Materials Testing Branch 5900 Folsom Blvd. Sacramento, CA 95819 916-227-7205 |
Contract # 040J7104 Cty SOL Rte 80 PM 1.8/4.4 Vendor # |
REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Quang Tran |
Date Reported: |
04/06/2022 |
|
Address: |
TL Number: |
TL 023652 |
||
City: |
||||
Project Name: RAISE BRIDGE AND PLACE STRUCTURAL CONCRETE. |
||||
Prime Contractor: BROSAMER & WALL, INC. |
||||
Sample Taken Date: |
03/09/2022 |
Mix Design: |
D30115EA |
|
Contractor: Unknown |
Location : SOLANO COUNTY IN VALLEJO AT VARIOUS LOCATIONS |
|||
Structure unique identifier: |
||||
Structure name: |
||||
Location of Pour: |
The following testing has been tested in accordance with:
ASTM C39-17a : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Specimen | Average diameter of cylinder (in) | Cross sectional area of cylinder (in^2) | Maximum load on cylinder (lb) | Compressive strength of cylinder (psi) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 4.02 | 12.69 | 47593 | 3750.0 | 1 |
2 | 4.02 | 12.69 | 39033 | 3075.0 | 1 |
3 | 4.02 | 12.69 | 49096 | 3868 | 1 |
DIME Test ID: 2022-03-09-12-1
Number of specimens: 3
Compressive strength (to nearest 10 psi): 3560
Age of specimen: 28 days
Certified By: Spencer Adams
*Subject to final inspection by the Resident Engineer. |
TL- Report of Laboratory Testing