Print Report | Back to Sample Detail

Sample Record for 2022-02-10-30

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 215145 DEA: 030H4604 EFIS: 0315000174 QA Service Level: 1
DIST-CO-RTE-PM: 03-PLA-80-2.6/3.1
Work Description: WIDEN ON-RAMP AND REPLACE BRIDGE.
Location Description: PLACER COUNTY IN ROSEVILLE AT THE ATLANTIC STREET ON RAMP
Contractor Name: Myers & Sons Construction
Contractor Address: 4600 Northgate Boulevard, Suite 100, Sacramento, CA 95834-1121
Resident Engineer: Justin Kunert Structure Rep.: Carl Anderson

Sample Information

DIME Sample ID: 2022-02-10-30
TL Number from the TL Form:
Sample Submitted By Organization: RMA Group - Rancho Cordova
Sample Organization Contact: (916) 631-7194
Type of Sample: Quality Control
Type of Material: Concrete
Sample Taken Date: 02/10/2022
Date that the sample was received by the laboratory/organization performing the testing: 02/10/2022
The quantity of what the sample constitutes: 100 cy
A brief description of the sample: Concrete
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Folsom Ready Mix

Material Information

The concrete mix design number: T71A5D1
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 4039070
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: Retaining Wall B abutment number 1
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 7

DIME Test ID: 2022-02-10-30-1
Test Method: CTM 557-June 2020: Method of Test for Temperature of Freshly Mixed Hydraulic Cement Concrete
Verified Date: 04/13/2022
Date Tested: 02/10/2022
Submitted By Organization: RMA Group - Rancho Cordova
Organization Address: 3150 Fitzgerald Road,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: mlowrance@rmacompanies.com
Organization Phone: (916) 631-7194
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Temperature 72 F

Test 2 of 7

DIME Test ID: 2022-02-10-30-2
Test Method: CTM 504-June 2010: Method of Test for Determining Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 04/13/2022
Date Tested: 02/10/2022
Submitted By Organization: RMA Group - Rancho Cordova
Organization Address: 3150 Fitzgerald Road,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: mlowrance@rmacompanies.com
Organization Phone: (916) 631-7194
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Air Content 1.8 %

Test 3 of 7

DIME Test ID: 2022-02-10-30-3
Test Method: CTM 518-June 2010: Method of Test for Unit Weight of Fresh Concrete
Verified Date: 04/13/2022
Date Tested: 02/10/2022
Submitted By Organization: RMA Group - Rancho Cordova
Organization Address: 3150 Fitzgerald Road,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: mlowrance@rmacompanies.com
Organization Phone: (916) 631-7194
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit weight of the concrete 151.3 lb/ft^3
Cement content 0 lb/yd^3

Test 4 of 7

DIME Test ID: 2022-02-10-30-4
Test Method: ASTM C143-20: Standard Test Method for Slump of Hydraulic-Cement Concrete
Verified Date: 04/13/2022
Date Tested: 02/10/2022
Submitted By Organization: RMA Group - Rancho Cordova
Organization Address: 3150 Fitzgerald Road,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: mlowrance@rmacompanies.com
Organization Phone: (916) 631-7194
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Slump 4.5 inch

Test 5 of 7

DIME Test ID: 2022-02-10-30-5
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/13/2022
Date Tested: 02/20/2022
Submitted By Organization: RMA Group - Rancho Cordova
Organization Address: 3150 Fitzgerald Road,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: mlowrance@rmacompanies.com
Organization Phone: (916) 631-7194
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 1
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 6.02 in
Compressive strength of cylinder (to nearest 10 psi) 4000 psi
Maximum load on cylinder 1 113980 lb
Type of fracture pattern of cylinder 1 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Age of specimen 10 days
Age of specimen in hours 0 hours

Test 6 of 7

DIME Test ID: 2022-02-10-30-6
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/13/2022
Date Tested: 02/18/2022
Submitted By Organization: RMA Group - Rancho Cordova
Organization Address: 3150 Fitzgerald Road,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: mlowrance@rmacompanies.com
Organization Phone: (916) 631-7194
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 1
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 6.00 in
Compressive strength of cylinder (to nearest 10 psi) 3680 psi
Maximum load on cylinder 1 104170 lb
Type of fracture pattern of cylinder 1 5
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Age of specimen 8 days
Age of specimen in hours 0 hours

Test 7 of 7

DIME Test ID: 2022-02-10-30-7
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 04/13/2022
Date Tested: 03/10/2022
Submitted By Organization: RMA Group - Rancho Cordova
Organization Address: 3150 Fitzgerald Road,
Organization City: Rancho Cordova
Organization State: CA
Organization Zipcode: 95742
Organization Email: mlowrance@rmacompanies.com
Organization Phone: (916) 631-7194
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 6.02 in
Average diameter of cylinder 2 6.00 in
Cross sectional area of cylinder 1 28.46 in^2
Cross sectional area of cylinder 2 28.27 in^2
Compressive strength (to nearest 10 psi) 4690 psi
Maximum load on cylinder 1 137100 lb
Maximum load on cylinder 2 128930 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 28 days
Age of specimen in hours 0 hours