Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project ID: 214951 DEA: 120K0234 EFIS: 1214000100
QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-5-17.1/18.9
Work Description: South County Improvement Project (Phase 3 - El Toro/Alicia) WIDEN FREEWAY AND BRIDGES, RECONSTRUCT BRIDGE AND WALLS.
Location Description: ORANGE COUNTY IN MISSION VIEJO, LAGUNA HILLS, LAGUNA WOODS AND LAKE FOREST FROM 0.4 MILE SOUTH OF ALICIA PARKWAY OVERCROSSING TO 0.2 MILE NORTH OF EL TORO ROAD UNDERCROSSING
Contractor Name: GUY F. ATKINSON CONSTRUCTION, LLC
Contractor Address: 18201 Von Karman Ave #800, Irvine, CA 92612
Resident Engineer: Irvin Nguyen Structure Rep.: Jason Kim
DIME Sample ID: 2022-02-08-2
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Quality Assurance
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 02/08/2022
Date that the sample was received by the laboratory/organization performing the testing: 02/15/2022
The quantity of what the sample constitutes: 1 of 14 Anchor bars
A brief description of the sample: F1554 Grade 55 HDG Anchor Bolts
From where was the sample collected: Manufacturer
Laboratory sample identification:
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Madden Bolt
Rocap Number(s):
Heat Number(s): 58048812
Nut Mfg. Lot Number(s): DEDW DECO
Washer Mfg. Lot Number(s): 0621-859
Bolt Specification: A529
Bolt Length(s): 5'-0"
Nut Specification: A563
Washer Specification: F436
Finish:
Diameter/Size: 2-1/2
Bolt Mfg. Lot Number:
Rocap Test Requirement(s):
Lubricant Requirements(s): waxed and dyed
DIME Test ID: 2022-02-08-2-1
Test Method: ASTM A370-20: Standard Test Methods and Definitions for Mechanical Testing of Steel Products (Tensile - Round Sample)
Verified Date: 02/23/2022
Date Tested: 02/17/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples
|
1
|
Sample | Heat Number | Diameter (in) | Area (sqin) | Stress at Offset (psi) | Tensile Strength (psi) | Elongation in 4 x d (%) | Tested By | 1A | L973M1 | 0.5 | 0.196 | 60944 | 84898 | 27.2 | spaine |
| |
UTM
|
67kip
|
Temperature
|
72 f
|
DIME Test ID: 2022-02-08-2-2
Test Method: ASTM A370-20: Standard Test Methods and Definitions for Mechanical Testing of Steel Products (Tensile - Round Sample)
Verified Date: 02/23/2022
Date Tested: 02/17/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of Samples
|
1
|
Sample | Heat Number | Diameter (in) | Area (sqin) | Stress at Offset (psi) | Tensile Strength (psi) | Elongation in 4 x d (%) | Tested By | 2 | L973M1 | 0.501 | 0.197 | 60747 | 84355 | 27.5 | spaine |
| |
UTM
|
67kip
|
Temperature
|
72 f
|
DIME Test ID: 2022-02-08-2-3
Test Method: ASME B1.2-83r17: (Ring Gage) Gages and Gaging for Unified Inch Screw Threads - Errata May 1992 (Ring Gage)
Verified Date: 02/23/2022
Date Tested: 02/17/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Sample No.
|
1A
|
Rocap Number
|
no data
|
Heat Number(s)
|
58048812
|
Mfg. Lot Number
|
no data
|
Finish Coating
|
Plain and ASTM F2329 - Hot Dip
|
Product Markings
|
YELLOW
|
Size
|
2.5 in
|
Bolt Length
|
60 in
|
Gage Type
|
Pass
|
DIME Test ID: 2022-02-08-2-4
Test Method: ASME B1.2-83r17: (Plug Gage) Gages and Gaging for Unified Inch Screw Threads - Errata May 1992 (Plug Gage)
Verified Date: 02/23/2022
Date Tested: 02/17/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Sample No.
|
1A
|
Rocap Number
|
no data
|
Heat Number(s)
|
no data
|
Mfg. Lot Number
|
DECO
|
Finish Coating
|
ASTM F2329 - Hot Dip
|
Product Markings
|
DH D/N 2H
|
Size
|
2.5 in
|
Gage Type
|
Pass
|
DIME Test ID: 2022-02-08-2-5
Test Method: ASME B1.2-83r17: (Plug Gage) Gages and Gaging for Unified Inch Screw Threads - Errata May 1992 (Plug Gage)
Verified Date: 02/23/2022
Date Tested: 02/17/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Sample No.
|
2A
|
Rocap Number
|
no data
|
Heat Number(s)
|
no data
|
Mfg. Lot Number
|
DEDW
|
Finish Coating
|
Plain
|
Product Markings
|
DH D/N 2H
|
Size
|
2.5 in
|
Gage Type
|
Pass
|
DIME Test ID: 2022-02-08-2-6
Test Method: ASTM B499-09r21: Standard Test Method for Measurement of Coating Thicknesses by the Magnetic Method: Nonmagnetic Coatings on Magnetic Basis Metals (Coating)
Verified Date: 02/23/2022
Date Tested: 02/17/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Sample No.
|
1A
|
Rocap Number
|
no data
|
Heat Number(s)
|
58048812
|
Mfg. Lot Number
|
no data
|
Finish Coating
|
Plain and ASTM F2329 - Hot Dip
|
Product Markings
|
YELLOW
|
Size
|
2.5 in
|
Bolt Length
|
60 in
|
Measurement Average
|
3.8 mils
|
DIME Test ID: 2022-02-08-2-7
Test Method: ASTM B499-09r21: Standard Test Method for Measurement of Coating Thicknesses by the Magnetic Method: Nonmagnetic Coatings on Magnetic Basis Metals (Coating)
Verified Date: 02/23/2022
Date Tested: 02/17/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Sample No.
|
1A
|
Rocap Number
|
no data
|
Heat Number(s)
|
no data
|
Mfg. Lot Number
|
DECO
|
Finish Coating
|
ASTM F2329 - Hot Dip
|
Product Markings
|
DH D/N 2H
|
Size
|
2.5 in
|
Bolt Length
|
no data in
|
Measurement Average
|
6.8 mils
|
DIME Test ID: 2022-02-08-2-8
Test Method: ASTM B499-09r21: Standard Test Method for Measurement of Coating Thicknesses by the Magnetic Method: Nonmagnetic Coatings on Magnetic Basis Metals (Coating)
Verified Date: 02/23/2022
Date Tested: 02/17/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Sample No.
|
1A
|
Rocap Number
|
no data
|
Heat Number(s)
|
no data
|
Mfg. Lot Number
|
0621-859
|
Finish Coating
|
ASTM F2329 - Hot Dip
|
Product Markings
|
F436 TSI
|
Size
|
2.5 in
|
Bolt Length
|
no data in
|
Measurement Average
|
7.97 mils
|
DIME Test ID: 2022-02-08-2-9
Test Method: ASTM E18-20: Standard Test Methods for Rockwell Hardness of Metallic Materials (Hardness)
Verified Date: 02/23/2022
Date Tested: 02/17/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Sample No.
|
1A
|
Rocap Number
|
no data
|
Heat Number(s)
|
no data
|
Mfg. Lot Number
|
DECO
|
Finish Coating
|
ASTM F2329 - Hot Dip
|
Product Markings
|
DH D/N 2H
|
Size
|
2.5 in
|
Bolt Length
|
no data in
|
Hardness Reading Scale
|
C Scale
|
Hardness Reading Average
|
29.58
|
Spacing
|
Ok
|
DIME Test ID: 2022-02-08-2-10
Test Method: ASTM E18-20: Standard Test Methods for Rockwell Hardness of Metallic Materials (Hardness)
Verified Date: 02/23/2022
Date Tested: 02/17/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Sample No.
|
2A
|
Rocap Number
|
no data
|
Heat Number(s)
|
no data
|
Mfg. Lot Number
|
DEDW
|
Finish Coating
|
Plain
|
Product Markings
|
DH D/N 2H
|
Size
|
2.5 in
|
Bolt Length
|
no data in
|
Hardness Reading Scale
|
C Scale
|
Hardness Reading Average
|
29.03
|
Spacing
|
Ok
|
DIME Test ID: 2022-02-08-2-11
Test Method: ASTM E18-20: Standard Test Methods for Rockwell Hardness of Metallic Materials (Hardness)
Verified Date: 02/23/2022
Date Tested: 02/17/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Sample No.
|
1A
|
Rocap Number
|
no data
|
Heat Number(s)
|
no data
|
Mfg. Lot Number
|
0621-859
|
Finish Coating
|
ASTM F2329 - Hot Dip
|
Product Markings
|
F436 TSI
|
Size
|
2.5 in
|
Bolt Length
|
no data in
|
Hardness Reading Scale
|
C Scale
|
Hardness Reading Average
|
41
|
Spacing
|
Ok
|