Sample Record for 2022-02-02-5
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 215236 DEA: 081C6804 EFIS: 0812000343
QA Service Level: 1
DIST-CO-RTE-PM: 08-RIV-74,79and371-Varies
Work Description: REPLACE STRUCTURAL CONCRETE BRIDGE, RETAINING WALL AND BOX CULVERT.
Location Description: RIVERSIDE COUNTY AT VARIOUS LOCATIONS
Contractor Name: Ortiz Enterprise
Contractor Address: 6 Cushing, Suite 200, Irvine, Ca 92618-4221
Resident Engineer: Nick Truong Structure Rep.: Arnel L. Vega
Sample Information
DIME Sample ID: 2022-02-02-5
TL Number from the TL Form:
Sample Submitted By Organization: CT HQ - QASI Los Angeles Field Office
Sample Organization Contact: (858) 285-5797
Type of Sample: Department Acceptance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 02/02/2022
Date that the sample was received by the laboratory/organization performing the testing: 02/15/2022
The quantity of what the sample constitutes: 4
A brief description of the sample: Mechanical Couplers
From where was the sample collected: Job Site
Laboratory sample identification:
Structure unique identifier: 56-0189
Structure name: Arroyo Seco bridge
The fabricator/manufacturer/facility name: Dayton Superior
Material Information
Production or Authorization Testing: Authorization Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: CMC
Coupler Manufacturer: Dayton Superior
Intermediate Assembler or Fabricator:
Rebar Size: #4
Coupler Model: Bar-Lock
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter:
Rebar Hoop Fabricator:
Coupler Component Heat/Lot Number(s): 4000003067
Rebar Heat Number(s): 2111442
Rebar Size 2 :
Coupler Unique ID:
Test Results
Test 1 of 3
DIME Test ID: 2022-02-02-5-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 02/23/2022
Date Tested: 02/23/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: ok necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 1 | | No. 4/13mm | 1 | -0.0024 | 0.2 | 20378 | 101890 | ok necking | spaine |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
Small
|
Test 2 of 3
DIME Test ID: 2022-02-02-5-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 02/23/2022
Date Tested: 02/23/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: ok necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 2 | | No. 4/13mm | 1 | 0 | 0.2 | 17790 | 88950 | ok necking | spaine |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
|
Test 3 of 3
DIME Test ID: 2022-02-02-5-4
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Cyclical/Fatique Tensile with Slip)
Verified Date: 02/23/2022
Date Tested: 02/23/2022
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: ok necking
Test Result Compliance:
Additional Comments When Verified:
Number of Samples Tested
|
1
|
Sample | Number of Cycles | Size | Mfg. Lot Number(s) | Slip (inch) | Area (sqin) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 3 | | No. 4/13mm | 1 | 0 | 0.2 | 17884 | 89420 | ok necking | spaine |
| |
UTM
|
400kip
|
Temperature
|
72.00 f
|
Halo ID
|
|