REPORT OF LABORATORY TESTING |
||||
Resident Engineer: |
Jarrett Woodruff |
Date Reported: |
11/24/2014 |
|
Address: |
TL Number: |
|
||
City: |
||||
Project Name: REPLACE BRIDGE. |
||||
Prime Contractor: VIKING CONSTRUCTION COMPANY, INC. |
||||
Sample Taken Date: |
10/27/2014 |
Mix Design: |
SF850AFST0 |
|
Contractor: Unknown |
Location : SLY PARK UNDERCROSSING |
|||
Structure unique identifier: 25 0042 |
||||
Structure name: Sly Park Rd UC |
||||
Location of Pour: |
The following testing has been tested in accordance with:
ASTM C1064-08: Standard Test Method for Temperature of Freshly Mixed Hydraulic-Cement Concrete
Temperature |
---|
70 |
DIME Test ID: 2014-10-27-1-1
Certified By: Brandon Miller
ASTM C143-10a: Standard Test Method for Slump of Hydraulic-Cement Concrete
Slump |
---|
8.5 |
DIME Test ID: 2014-10-27-1-2
Certified By: Brandon Miller
ASTM C231-10: Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
Air content |
---|
5.3 |
DIME Test ID: 2014-10-27-1-3
Certified By: Brandon Miller
ASTM C39-10 : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Specimen | Cross sectional area of cylinder (in^2) | Average diameter of cylinder (in) | Compressive strength of cylinder (psi) | Maximum load on cylinder (lb) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 27.9 | 5.96 | 4354.1 | 121478 | 1 |
2 | 28.46 | 6.02 | 4267.4 | 121451 | 1 |
DIME Test ID: 2014-10-27-1-4
Number of specimens: 2
Compressive strength (to nearest 10 psi): 4310
Comment on any defect in either specimen or caps (Max 250 Characters):
Age of specimen: 7 days
Certified By: She Vang
ASTM C39-10 : Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Capped in accordance with ASTM C617/CTM521
Cured in accordance with ASTM C511
Specimen | Cross sectional area of cylinder (in^2) | Average diameter of cylinder (in) | Compressive strength of cylinder (psi) | Maximum load on cylinder (lb) | Type of fracture pattern of cylinder |
---|---|---|---|---|---|
1 | 28.09 | 5.98 | 5707.5 | 160325 | 1 |
2 | 28.46 | 6.02 | 5782.8 | 164578 | 1 |
DIME Test ID: 2014-10-27-1-5
Number of specimens: 2
Compressive strength (to nearest 10 psi): 5750
Age of specimen: 28 days
Certified By: She Vang
*Subject to final inspection by the Resident Engineer. |
![]() |
TL- Report of Laboratory Testing