Sample Record for 2022-01-07-3

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

Project ID: 214671 DEA: 07303904 EFIS: 0714000044 QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-10-31.2/37.2
Work Description: LANE REPLACEMENT
Location Description: LOS ANGELES COUNTY IN BALDWIN PARK AND WEST COVINA FROM 0.1 MILE EAST OF THE 10/605 SEPARATION TO 0.3 MILE WEST OF CITRUS STREET OVERCROSSING
Contractor Name: Sierra Landscape Development Inc.
Contractor Address: 2209 1/2 Chico Ave., South El Monte CA, 91733
Resident Engineer: Hai Hong Structure Rep.: Unknown

Sample Information

DIME Sample ID: 2022-01-07-3
TL Number from the TL Form:
Sample Submitted By Organization: Kleinfelder, Incorporated - Los Angeles
Sample Organization Contact: (909) 833-5780
Type of Sample: Per Request
Type of Material: Concrete
Sample Taken Date: 01/07/2022
Date that the sample was received by the laboratory/organization performing the testing: 01/07/2022
The quantity of what the sample constitutes: Trail Batch
A brief description of the sample: A set of 6 LCB RS cylinders
From where was the sample collected: Source
Laboratory sample identification: 220026
Structure unique identifier:
Structure name: Trial Batch
The fabricator/manufacturer/facility name: Security Paving Burbank Batch Plant

Material Information

The concrete mix design number: G322LRS271
The truck number from where the sample was collected: Load 1
The batch plant ticket number from where the sample was collected: 224686
Concrete batch plant: Security Paving Burbank Batch Plant
The fabricator/manufacturer designation for the sample: Trial Batch
A detailed description of where the material sample was collected: Concrete from wheelbarrow
Where the material sample would have been placed if not sampled: Trial slab
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 4

DIME Test ID: 2022-01-07-3-1
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Verified Date: 01/07/2022
Date Tested: 01/07/2022
Submitted By Organization: Kleinfelder, Incorporated - Los Angeles
Organization Address: 620 South Magnolia Avenue, Building G,
Organization City: Ontario
Organization State: CA
Organization Zipcode: 91762
Organization Email: mdorsch@kleinfelder.com
Organization Phone: (909) 833-5780
General Comments for this Test: Witness QC break a set of 2 opening age LCB RS cylinders with average results of 240psi at 5 hours. All unknown values have a zero listed above.
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Apparent mass of submerged cylinder 1 0 lb
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.00 in
Cross sectional area of cylinder 1 0 in^2
Cross sectional area of cylinder 2 0 in^2
Compressive strength (to nearest 10 psi) 240 psi
Maximum load on cylinder 1 0 lb
Maximum load on cylinder 2 0 lb
Type of fracture pattern of cylinder 1 4
Type of fracture pattern of cylinder 2 4
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1.00
Correction factor for cylinder 2 1.00
Age of specimen 0 days
Age of specimen in hours 5 hours
Serial number of delivery ticket, if available no data

Test 2 of 4

DIME Test ID: 2022-01-07-3-2
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 01/17/2022
Date Tested: 01/14/2022
Submitted By Organization: Kleinfelder, Incorporated - Los Angeles
Organization Address: 620 South Magnolia Avenue, Building G,
Organization City: Ontario
Organization State: CA
Organization Zipcode: 91762
Organization Email: mdorsch@kleinfelder.com
Organization Phone: (909) 833-5780
General Comments for this Test: 7 day breaks for log # 220027 for sample 1-7-1/2 & 1-7-2/2
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 6.02 in
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.46 in^2
Compressive strength (to nearest 10 psi) 3620 psi
Maximum load on cylinder 1 105410 lb
Maximum load on cylinder 2 99650 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days
Age of specimen in hours 0 hours

Test 3 of 4

DIME Test ID: 2022-01-07-3-3
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 01/17/2022
Date Tested: 01/14/2022
Submitted By Organization: Kleinfelder, Incorporated - Los Angeles
Organization Address: 620 South Magnolia Avenue, Building G,
Organization City: Ontario
Organization State: CA
Organization Zipcode: 91762
Organization Email: mdorsch@kleinfelder.com
Organization Phone: (909) 833-5780
General Comments for this Test: 7 day breaks for log # 220028 for sample 2-7-1/2 & 2-7-2/2
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 6.00 in
Average diameter of cylinder 2 6.01 in
Cross sectional area of cylinder 1 28.27 in^2
Cross sectional area of cylinder 2 28.37 in^2
Compressive strength (to nearest 10 psi) 3610 psi
Maximum load on cylinder 1 101540 lb
Maximum load on cylinder 2 103090 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days
Age of specimen in hours 0 hours

Test 4 of 4

DIME Test ID: 2022-01-07-3-4
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 01/17/2022
Date Tested: 01/14/2022
Submitted By Organization: Kleinfelder, Incorporated - Los Angeles
Organization Address: 620 South Magnolia Avenue, Building G,
Organization City: Ontario
Organization State: CA
Organization Zipcode: 91762
Organization Email: mdorsch@kleinfelder.com
Organization Phone: (909) 833-5780
General Comments for this Test: 7 day breaks for log # 220029 for sample 3-7-1/2 & 3-7-2/2
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 2
Test performed With no density determined
Capped in accordance with? ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1 5.99 in
Average diameter of cylinder 2 6.02 in
Cross sectional area of cylinder 1 28.18 in^2
Cross sectional area of cylinder 2 28.46 in^2
Compressive strength (to nearest 10 psi) 3520 psi
Maximum load on cylinder 1 101090 lb
Maximum load on cylinder 2 98160 lb
Type of fracture pattern of cylinder 1 3
Type of fracture pattern of cylinder 2 3
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Age of specimen 7 days
Age of specimen in hours 0 hours